Trane BCXC-SVX01B-EN, BCHC manual Belt tension, BCBH/BCVC valve package waterflow limits

Page 65

Maintenance

NOTICE

Belt tension!

Do not over-tension belts. Excessive belt tension will reduce fan and motor bearing life, accelerate belt wear, and could result in shaft failure.

Table 32. BCHC/BCVC fan, filter, and mixing box general data

Unit size

12

18

24

36

54

72

90

Nominal cfm

400

600

800

1200

1800

2400

3000

 

 

 

 

 

 

 

 

Air flow

 

 

 

 

 

 

 

Minimum cfm

250

375

500

750

1125

1500

1875

Maximum cfm

500

675

1000

1600

2400

3000

4000

 

 

 

 

 

 

 

 

Fan data

 

 

 

 

 

 

 

Fan wheel, in. (dia. x width)

9.5 x 4.5

9.5 x 4.5

9.5 x 9.5

9.5 x 9.5

12.6 x 9.5

12.6 x 9.5

12.6 x 9.5

Maximum rpm

2300

2300

1800

1800

1500

1500

1500

Motor hp

0.33–1.0

0.33–1.0

0.33–1.0

0.33–1.5

0.33–2.0

0.33–3.0

0.33–3.0

 

 

 

 

 

 

 

 

Unit flat filter

 

 

 

 

 

 

 

Qty. - size, in.

1 - 12 x 24 1 - 12 x 24 1 - 16 x 25 2 - 16 x 20 2 - 20 x 20 1 - 20 x 20 3 - 16 x 25

 

 

 

 

 

 

1 - 20 x 25

 

Area, sq. ft

2.000

2.000

2.778

4.444

5.556

6.250

8.333

Velocity, ft/min.

200

300

288

270

324

384

360

 

 

 

 

 

 

 

 

Angle filter

 

 

 

 

 

 

 

Qty. - size, in.

2 - 12 x 24 2 - 12 x 24 2 - 12 x 24 2 - 20 x 20 4 - 16 x 20 4 - 16 x 20 4 - 20 x 20

Area, sq. ft

4.000

4.000

4.000

5.556

8.889

8.889

11.111

Velocity, ft/min.

100

150

200

216

203

270

270

 

 

 

 

 

 

 

Bottom / top access filter box

 

 

 

 

 

 

Qty. - size, in.

1 - 12 x 20 1 - 12 x 24 1 - 16 x 25 1 - 16 x 20 1 - 16 x 20 1 - 20 x 25 2 - 16 x 25

 

 

 

 

1 - 16 x 16 1 - 20 x 20 1 - 20 x 20 1 - 14 x 25

Area, sq. ft

1.700

2.000

2.800

4.000

5.000

6.300

8.000

Velocity, ft/min.

240

300

288

300

360

384

375

 

 

 

 

 

 

 

 

Mixing box

 

 

 

 

 

 

 

Damper opening width, in.

15.5

19.5

19.5

31.5

31.5

31.5

31.5

Damper opening height, in.

7

7

7

7

12.75

12.75

12.75

Area, sq. ft

0.753

0.948

0.948

1.531

2.789

2.789

2.789

Velocity, ft/min.

531

633

844

784

645

861

1076

Note: Minimum air flow limits apply to units with hot water or electric heat only. There is no minimum airflow limit on cooling on units. Maximum airflow limits are to help prevent moisture carryover.

Table 33. BCBH/BCVC valve package waterflow limits

Tube size (in.)

gpm

 

 

1/2

8.6

 

 

3/4

19.3

 

 

1

34.3

 

 

1-1/4

53.5

 

 

BCXC-SVX01B-EN

65

Image 65
Contents April Blower Coil Air HandlerResponsible Refrigerant Practices Refrigerant warning informationEnvironmental Concerns Hazard of Explosion and Deadly Gases Trademarks About This ManualTable of Contents BCXC-SVX01B-EN Digits 1, 2, 3, 4 Unit Model Digit 16 Motor HorsepowerDigits 5, 6, 7 Unit Size Digit 8 Unit VoltageModel Number Description Blower Coil General Information General InformationGeneral Information Jobsite Storage Recommendations Pre-InstallationReceiving and Handling Service Access Installation PreparationPre-Installation Unit size Dimension aRigging and Handling Unit Handling ProcedureImproper Unit Lift Unit Location RecommendationsSkid Removal Pre-Installation ChecklistHorizontal blower coil dimensions in. and weights lb Dimensions and WeightsUnit Size RH LH Weight Horizontal Blower CoilVertical blower coil dimensions in. and weights lb Dimensions and WeightsUnit Size Weight Vertical Blower CoilUnit size Angle filter and mixing box dimensions in. and weights lbAngle Filter and Mixing Box AIR Flow Filter Filter Access Panel Bottom or Top Access Filter BoxElectric Heat Electric heat dimensions in. and weights lbSteam Coil Steam coil box dimensions in. and weights lbCoil Connections, NPT Supply ReturnHydronic coil connection sizes, OD Coil ConnectionsDX coil connection sizes, OD Steam coil connection sizes, female connection, NPTBasic Piping Piping PackagesDimensions and Weights Deluxe Piping Actual size Piping NominalInstalling Wall Mounted Controls Installation ControlsZone Sensor Installation Wiring InstructionsInstallation Controls Communication WiringService Communication Wiring Zone Sensors Without Interconnecting WiringTracer Summit Communication Wiring Installation Electrical Zone sensor maximum wiring distances, ft m Installation ElectricalWire size range Max. wiring distance Electrical Grounding Restrictions Hazardous VoltageUnit size Voltage Useful FormulasAvailable electric heat, min-max kW Motor electrical data 240/50/1 220/50/1190/50/3 380/50/3Installing the Unit Installation MechanicalBchc Installation Procedure Horizontal Units, Model BchcVertical Units, Model Bcvc Installation MechanicalMixing Box Option Heating Coil OptionCondensate Drain Connections Mixing Box Installation ProcedureLinkage Installation Procedure Duct Connections Recommended drain trap installation for draw-through unitsWater Coil Connections Installation PipingPotential coil-freeze condition Refrigerant Coil PipingSuction Line Installation PipingValve Damage Field-installed evaporation piping example Field-Installing Evaporator PipingCoil Condensate Steam PipingGeneral Steam CoilsType NS steam coils, horizontal tubes for horizontal airflow Tracer Controllers Controls InterfaceControl Options Controls Interface Rover Service SoftwareTracer controller input/output summary Tracer controller ZN010 ZN510 ZN520Tracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Tracer controller function summaryEnd Device Option Availability Pre-Start Pre-Start ChecklistReceiving Unit LocationDuctwork Pre-Start Component OverviewUnit Piping ElectricalTracer ZN Controller Sequence of Operation Start-UpSequence of Operation Unoccupied Mode Occupied ModeSensor type Sensor position Unit occupancy mode Start-UpOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Occupied Standby Mode Tracer ZN510 or ZN520 onlyCooling Operation DX Cooling Tracer ZN520 only Start-Up Economizer Cooling Tracer ZN520 OnlyDischarge Air Tempering Tracer ZN520 Only Heating OperationTracer ZN520 fan configuration Fan Mode Operation Rotating ComponentsAuto fan operation Fan speed default Fan sequence of operationTracer ZN010 and ZN510 Fan Speed SwitchTracer ZN520 Continuous Fan OperationFan mode operation, Tracer ZN010 and ZN510 Fan Off DelayStart-Up Fan Cycling Operation Fan Start on High SpeedLocal fan switch enabled Entering Water Temperature Sampling FunctionTwo- and Four-Pipe Changeover Operation Fan operation in heating and cooling modesUnit type EWT sensor required? Coil water temperature Unit mode as related to water temperatureElectric Heat Operation Economizer Damper Tracer ZN520 OnlyTracer Dehumidification Tracer ZN520 Only BIP1 Low Temperature Detection OptionData Sharing Tracer ZN510 or ZN520 Only Binary InputsBIP2 Condensate Overflow Detection Option Binary input configurationsBIP3 Occupancy Sensor BIP4 Fan Status ZN520 OnlyBinary Outputs Analog InputsAnalog inputs Analog input Terminal Function Range ZN010 ZN510 ZN520Binary output configuration Space Temperature MeasurementZone sensor wiring connections Zone SensorExternal Setpoint Adjustment Fan Mode SwitchFan Switch Local SetpointCommunication Jack On/Cancel ButtonsMaintenance Procedures MaintenanceFan Assembly Set Screws MaintenanceFan Belt Tension Torque in.-lb Ft-lbBCBH/BCVC valve package waterflow limits Belt tensionRow coil BCHC/BCVC coil general dataHydronic coil data Steam coil data 1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Drive dataUnit Motor Motor sheave Fan sheave Belt Potential unit damage from coil cleaners Coil MaintenanceInspecting and Cleaning Coils Steam, Hot Water, and Cooling Coil Cleaning ProcedureRotating parts Periodic Maintenance ChecklistsMaintenance LED Activity DiagnosticsTroubleshooting Manual Output Test DiagnosticsManual Output Test Procedure Translating Multiple Diagnostics DiagnosticsTracer ZN520 test sequence Fan Cool output a Heat output Damper Steps J1-1, J1-3Automatic Reset by the Controller Resetting DiagnosticsCycling Power Diagnostics Manual Output TestRover Service Tool Diagnostic Reset Tracer ZN510 or ZN520 OnlyTracer ZN520 diagnostics Tracer ZN010 and ZN510 controller diagnosticsDiagnostic Latching Fan Valves Electric heat Damper Diagnostic Fan Other outputsaFan outputs do not energize Common DiagnosticsValves stay closed Probably cause ExplanationFresh air damper stays closed Valves stay openElectric heat not operating DX or electric outputs do not energize Fresh air damper stays openTwo-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Bcxc with DX Coil and Tracer ZN520 Field Installed DeviceBcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN