Trane BCXC-SVX01B-EN, BCVC, BCHC manual Analog Inputs, Binary Outputs, Analog inputs

Page 59

Start-Up

Analog Inputs

See Table 28 for a complete description of analog inputs.

Table 28. Analog inputs

Analog input

Terminal

Function

Range

ZN010

ZN510

ZN520

 

 

 

 

 

 

 

Zone

TB3-1

Space temperature input

5° to 122°F (-15° to 50°C)

 

 

 

 

 

 

 

Ground

TB3-2

Analog ground

N/A

 

 

 

 

 

 

 

Set

TB3-3

Setpoint input

40° to 115°F (4.4° to 46.1°C)

 

 

 

 

 

 

 

Fan

TB3-4

Fan switch input

4821 to 4919 W (Off)

 

 

 

2297 to 2342 W (Auto)

 

 

 

 

 

 

10593 to 10807 W (Low)

 

 

 

 

 

 

15137 to 16463 W (High)

 

 

 

 

 

 

 

 

 

 

Ground

TB3-6

Analog ground

N/A

 

 

 

 

 

 

 

Analog Input 1

J3-1

Entering water temperature

-40° to 212°F (-40° to 100°C)

 

J3-2

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 2

J3-3

Discharge air temperature

-40° to 212°F (-40° to 100°C)

 

J3-4

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 3

J3-6

Fresh air temp/generic temp

-40° to 212°F (-40° to 100°C)

 

 

 

 

Analog ground

N/A

 

 

 

 

 

 

 

 

 

 

Analog Input 4

J3-7

Universal Input

0 – 100%

 

 

 

 

Generic 4-20 ma

0 – 100%

 

 

 

 

 

Humidity

0 – 2000ppm

 

 

 

 

 

CO2

 

 

 

 

 

 

 

 

 

 

 

Ground

J3-8

Analog ground

N/A

 

 

 

 

 

 

 

 

 

Ground

J3-9

Analog ground

N/A

 

 

Notes:

1.The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10KW thermistors.

2.Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board.

3.Changeover units include an entering water temperature sensor.

Binary Outputs

Binary outputs are configured to support the following:

Two fan stages (when one or two fan stages are present, J1-2 can be configured as exhaust fan)

One hydronic cooling stage

One hydronic heating stage (dehumidification requires this to be in the reheat position)

One DX cooling stage

One or two-stage electric heat (dehumidification requires this to be in the reheat position)

Face and bypass damper

Modulating fresh air damper (Tracer™ ZN520 only)

One-stage baseboard heat

BCXC-SVX01B-EN

59

Image 59
Contents April Blower Coil Air HandlerResponsible Refrigerant Practices Refrigerant warning informationEnvironmental Concerns Hazard of Explosion and Deadly Gases Trademarks About This ManualTable of Contents BCXC-SVX01B-EN Digit 8 Unit Voltage Digit 16 Motor HorsepowerDigits 1, 2, 3, 4 Unit Model Digits 5, 6, 7 Unit SizeModel Number Description Blower Coil General Information General InformationGeneral Information Jobsite Storage Recommendations Pre-InstallationReceiving and Handling Unit size Dimension a Installation PreparationService Access Pre-InstallationUnit Location Recommendations Unit Handling ProcedureRigging and Handling Improper Unit LiftSkid Removal Pre-Installation ChecklistHorizontal Blower Coil Dimensions and WeightsHorizontal blower coil dimensions in. and weights lb Unit Size RH LH WeightVertical Blower Coil Dimensions and WeightsVertical blower coil dimensions in. and weights lb Unit Size WeightUnit size Angle filter and mixing box dimensions in. and weights lbAngle Filter and Mixing Box AIR Flow Filter Filter Access Panel Bottom or Top Access Filter BoxElectric Heat Electric heat dimensions in. and weights lbSupply Return Steam coil box dimensions in. and weights lbSteam Coil Coil Connections, NPTSteam coil connection sizes, female connection, NPT Coil ConnectionsHydronic coil connection sizes, OD DX coil connection sizes, ODBasic Piping Piping PackagesDimensions and Weights Deluxe Piping Actual size Piping NominalWiring Instructions Installation ControlsInstalling Wall Mounted Controls Zone Sensor InstallationZone Sensors Without Interconnecting Wiring Communication WiringInstallation Controls Service Communication WiringTracer Summit Communication Wiring Installation Electrical Electrical Grounding Restrictions Hazardous Voltage Installation ElectricalZone sensor maximum wiring distances, ft m Wire size range Max. wiring distanceUnit size Voltage Useful FormulasAvailable electric heat, min-max kW Motor electrical data 380/50/3 220/50/1240/50/1 190/50/3Horizontal Units, Model Bchc Installation MechanicalInstalling the Unit Bchc Installation ProcedureVertical Units, Model Bcvc Installation MechanicalMixing Box Option Heating Coil OptionCondensate Drain Connections Mixing Box Installation ProcedureLinkage Installation Procedure Duct Connections Recommended drain trap installation for draw-through unitsRefrigerant Coil Piping Installation PipingWater Coil Connections Potential coil-freeze conditionSuction Line Installation PipingValve Damage Field-installed evaporation piping example Field-Installing Evaporator PipingSteam Coils Steam PipingCoil Condensate GeneralType NS steam coils, horizontal tubes for horizontal airflow Tracer Controllers Controls InterfaceControl Options Tracer controller ZN010 ZN510 ZN520 Rover Service SoftwareControls Interface Tracer controller input/output summaryTracer Control Device ZN010 Tracer ZN510 Tracer ZN520 Tracer controller function summaryEnd Device Option Availability Unit Location Pre-Start ChecklistPre-Start ReceivingElectrical Pre-Start Component OverviewDuctwork Unit PipingTracer ZN Controller Sequence of Operation Start-UpSequence of Operation Start-Up Occupied ModeUnoccupied Mode Sensor type Sensor position Unit occupancy modeOccupied Bypass Mode, Tracer ZN510 or ZN520 Only Occupied Standby Mode Tracer ZN510 or ZN520 onlyCooling Operation Heating Operation Start-Up Economizer Cooling Tracer ZN520 OnlyDX Cooling Tracer ZN520 only Discharge Air Tempering Tracer ZN520 OnlyFan sequence of operation Fan Mode Operation Rotating ComponentsTracer ZN520 fan configuration Auto fan operation Fan speed defaultContinuous Fan Operation Fan Speed SwitchTracer ZN010 and ZN510 Tracer ZN520Fan Start on High Speed Fan Off DelayFan mode operation, Tracer ZN010 and ZN510 Start-Up Fan Cycling OperationFan operation in heating and cooling modes Entering Water Temperature Sampling FunctionLocal fan switch enabled Two- and Four-Pipe Changeover OperationEconomizer Damper Tracer ZN520 Only Unit mode as related to water temperatureUnit type EWT sensor required? Coil water temperature Electric Heat OperationBinary Inputs BIP1 Low Temperature Detection OptionTracer Dehumidification Tracer ZN520 Only Data Sharing Tracer ZN510 or ZN520 OnlyBIP4 Fan Status ZN520 Only Binary input configurationsBIP2 Condensate Overflow Detection Option BIP3 Occupancy SensorAnalog input Terminal Function Range ZN010 ZN510 ZN520 Analog InputsBinary Outputs Analog inputsZone Sensor Space Temperature MeasurementBinary output configuration Zone sensor wiring connectionsLocal Setpoint Fan Mode SwitchExternal Setpoint Adjustment Fan SwitchCommunication Jack On/Cancel ButtonsMaintenance Procedures MaintenanceTorque in.-lb Ft-lb MaintenanceFan Assembly Set Screws Fan Belt TensionBCBH/BCVC valve package waterflow limits Belt tensionRow coil BCHC/BCVC coil general dataHydronic coil data Steam coil data 1750 1450 Size Watts Browning Trane 60 Hz 50 Hz Drive dataUnit Motor Motor sheave Fan sheave Belt Steam, Hot Water, and Cooling Coil Cleaning Procedure Coil MaintenancePotential unit damage from coil cleaners Inspecting and Cleaning CoilsRotating parts Periodic Maintenance ChecklistsMaintenance LED Activity DiagnosticsTroubleshooting Manual Output Test DiagnosticsManual Output Test Procedure Fan Cool output a Heat output Damper Steps J1-1, J1-3 DiagnosticsTranslating Multiple Diagnostics Tracer ZN520 test sequenceAutomatic Reset by the Controller Resetting DiagnosticsDiagnostic Reset Tracer ZN510 or ZN520 Only Diagnostics Manual Output TestCycling Power Rover Service ToolDiagnostic Fan Other outputsa Tracer ZN010 and ZN510 controller diagnosticsTracer ZN520 diagnostics Diagnostic Latching Fan Valves Electric heat DamperProbably cause Explanation Common DiagnosticsFan outputs do not energize Valves stay closedFresh air damper stays closed Valves stay openElectric heat not operating DX or electric outputs do not energize Fresh air damper stays openTwo-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Wiring DiagramsFour-Pipe Bcxc with Tracer ZN510 Two-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Tracer ZN520 Four-Pipe Bcxc with Control Interface Four-Pipe Bcxc with Control Interface Bcxc with DX Coil and Tracer ZN520 Field Installed DeviceBcxc with DX Coil, Hydronic Heating, and Tracer ZN520 BCXC-SVX01B-EN