Diagnostics
Table 41. Tracer ZN010 and ZN510 controller diagnostics
Diagnostic | Latching | Fan | Valves | Electric heat | Damper |
|
|
|
|
|
|
Auxiliary temperature failure | No | Enabled | No action | No action | No action |
|
|
|
|
|
|
Condensate overflow detection | Yes | Off | Closed | Off | Closed |
|
|
|
|
|
|
Entering water temperature | No | Enabled | Enabled | Enabled | Enabled |
|
|
|
|
|
|
Fan mode failure | No | Enabled | Enabled | Enabled | Enabled |
|
|
|
|
|
|
Invalid unit configuration failure | Yes | Disabled | Disabled | Disabled | Disabled |
|
|
|
|
|
|
Low temperature detection | Yes | Off | Open | Off | Closed |
|
|
|
|
|
|
Maintenance required | Yes | Enabled | No action | No action | No action |
|
|
|
|
|
|
Setpoint | No | Enabled | No action | No action | No action |
|
|
|
|
|
|
Zone temperature failure | No | Off | Closed | Off | Closed |
Notes:
1.Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics affect unit operation according to priority level.
2.Latching: A latching diagnostic requires a manual reset of the controller; while a
3.Enabled: End device is allowed to run if there is a call for it to run.
4.Disabled: End device is not allowed to run even if there is a call for it to run.
5.No Action: The diagnostic has no affect on the end device.
Table 42. Tracer ZN520 diagnostics
Diagnostic | Fan | Other outputs(a) |
Condensate overflow | Off | Valves closed, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Low temperature detection | Off | Valves open, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Low air flow - fan failure | Off | Valves closed, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Space temperature failure | Off | Valves closed, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Entering water temperature failure | On | Valves enabled(b), fresh air damper enabled(b), electric heat enabled(b), baseboard heat off |
Discharge air temperature low limit | Off | Valves open, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Discharge air temperature failure | Off | Valves closed, fresh air damper closed, electric heat off, baseboard heat off |
|
|
|
Fresh air temperature failure | On | Valves enabled, fresh air damper minimum position(c), electric heat enabled, baseboard heat |
|
| enabled |
|
|
|
Relative humidity failure | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
Generic | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
CO2 input failure | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
Maintenance required | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
Local fan mode failure | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
Local setpoint failure | On | Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled |
|
|
|
Invalid unit configuration | Off | Valves disabled, fresh air damper disabled, electric heat disabled, baseboard heat disabled |
|
|
|
Normal - power up | On | Valves enabled, fresh air damper enabled, electric heat enabled |
(a)The generic binary output
(b)When the entering water temperature is required but not present, the Tracer™ ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid entering water temperature value is present
(c)When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present
| 77 |