Diagnostics
Common Diagnostics
Table 43. Fan outputs do not energize
Probably cause | Explanation |
|
|
Random start observed | After |
| remains off until the random start time expires. |
| When |
| 1. The controller exits |
| 2. The controller exits |
Cycling fan operation | When the fan mode switch is in the auto position, the unit fan cycles off when there is no call for heating or cooling. |
| The heating/cooling sources cycle on or off periodically with the unit fan to match the capacity according to pulse width |
| modulation (PWM) logic. |
Unoccupied operation | The fan cycles with capacity when the unit is in unoccupied mode. This occurs even if the unit is in continuous fan |
| operation. While unoccupied, the fan cycles on or off with heating/cooling to provide varying amounts of heating or |
| cooling to the space. to match the capacity diagnostics according to |
Fan mode off | When using the local fan mode switch to determine the fan operation, the off position controls the unit fan to off. |
Requested mode: off | It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When “off” is |
| communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the |
| controller is in this mode. |
Diagnostic present | A specific list of diagnostics affects fan operation. For more information, see Table 41, p. 77 and Table 42, p. 77. |
No power to the | If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN controller to operate normally, |
controller | it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient |
| power or has failed. |
Unit configuration | The controller must be properly configured based on the actual installed end devices and application. When the unit |
| configuration does not match the actual end devices, the valves may not work correctly. |
Manual output test | The controller includes a manual output test sequence to verify binary output operation and the associated wiring. |
| However, based on the current step in the test sequence, the unit fan may not be powered on. Refer to “Manual Output |
| Test,” p. 73. |
Unit wiring | The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan |
| operation. Refer to the specific unit wiring diagrams on the unit. |
|
|
Table 44. Valves stay closed
Probable cause | Explanation |
|
|
Normal operation | The controller opens and closes the valves to meet the unit capacity requirements. |
Requested mode: off | It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When off is |
| communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the |
| controller is in this mode. |
Valve override | The controller can communicate a valve override request.This request affects the valve operation. |
Manual output test | The controller includes a manual output test sequence to verify analog and binary output operation and the associated |
| wiring. However, based on the current step in the test sequence, the valves may not be open. Refer to the “Manual |
| Output Test,” p. 73. |
Diagnostic present | A specific list of diagnostics affects valve operation. For more information, see Table 41, p. 77 and Table 42, p. 77. |
Sampling logic | The controller includes entering water temperature sampling logic that automatically invokes during |
| changeover. It determines when the entering water temperature is either too cool or too hot for the desired heating |
| or cooling mode. Refer to “Entering Water Temperature Sampling Function,” p. 55. |
Unit configuration | The controller must be properly configured based on the actual installed end devices and application. When the unit |
| configuration does not match the actual end device, the valves may not work correctly. |
No power to the | If the controller does not have power, the unit fan does not operate. For the Tracer™ ZN010, 510 controller to operate |
controller | normally, it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have |
| sufficient power or has failed. |
Unit wiring | The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation. |
| Refer to the unit wiring diagrams on the unit. |
|
|
78 |
|