Kohler 6VSG, 24VDC, 36VDC, 48VDC manual Resetting the Controller After a Fault Shutdown

Page 20

2.6.3Resetting the Controller After a Fault Shutdown

Always identify and correct the cause of a fault shutdown before resetting the controller. Check the fault message displayed on the controller and refer to Figure 2-5to identify and correct the fault condition

before proceeding. Contact an authorized distributor/dealer for service, if necessary.

Press the OFF button to reset the controller, or follow the procedure below. See Figure 2-4.

1.While the fault message is displayed, press the Select button to go to the Overview menu.

2.Press Select again. The active fault message is displayed.

3.Press Select. Confirm Clear Fault: NO is displayed.

4.Press the UP arrow button. Confirm Clear Fault: YES is displayed.

5.Press the Select button to enter YES and clear the fault.

6.Press the Select button to return to the overview menu. The controller changes to OFF mode.

7.Press AUTO to put the generator set into automatic mode.

Fault Message

Overview ---->

Fault Message

Confirm Clear

 

1.2 h

 

Fault: NO

 

 

 

Press UP

 

 

 

arrow button.

 

 

 

Confirm Clear

 

 

 

Fault: YES

 

 

 

tp6809

Figure 2-4Clearing a Fault on the VSC Controller

 

Warning (W) or

 

 

Fault Message

Shutdown(SD)

Condition

Check

 

 

 

 

Accy PwrOver

W

Accessory Power Overload. Too many devices

Contact an authorized

Warning

 

on the accessory power port or an over current

distributor/dealer for service.

 

 

fault (short circuit) on the accessory controller

 

 

 

power output. (Feeds RBUS devices - PIM)

 

 

 

 

 

Aux Input

SD *

Auxiliary input. An optional customer-connected

Check customer-supplied equipment.

 

 

input is closed. (Digital input from optional PIM.)

 

 

 

 

 

Batt Chg Flt

W

Battery charger fault. Input to PIM from an

Check external battery charger.

 

 

external battery charger (not the built-in battery

 

 

 

charger).

 

 

 

 

 

Battery Voltage

W

Engine starting battery voltage is critically low,

Check the battery rating and

CrLow

 

less than 10.5 VDC.

condition.

 

 

 

Check the battery charger operation.

 

 

 

Charge or replace the battery.

 

 

 

 

Battery Voltage

W

Engine starting battery voltage rises above

Check the battery rating and

High

 

16 VDC for more than 10 seconds. Inhibited

condition.

 

 

during the engine crank cycle.

Check the battery charger operation.

 

 

Clears when the battery voltage returns to an

 

 

 

 

 

acceptable level.

 

 

 

 

 

Battery Voltage

W

Engine starting battery voltage falls below

Check the battery rating and

Low

 

12.5 VDC for more than 90 seconds when the

condition.

 

 

engine is not running.

Check the battery charger operation.

 

 

Not operative during the engine crank cycle.

 

 

Charge or replace the battery.

 

 

Clears when the battery voltage returns to an

 

 

 

acceptable level.

 

 

 

 

 

20 Section 2 Generator Set Operation

TP-6843 1/13

Image 20
Contents VSC TP-6843 1/13aProduct Identification Information Controller IdentificationGenerator Set Identification Numbers Engine IdentificationTable of Contents Appendix a Abbreviations Table of ContentsScheduled Maintenance Accidental Starting Safety Precautions and InstructionsBattery Engine Backfire/Flash Fire Exhaust SystemUse extreme care when handling, storing, and using fuels Fuel System Hazardous NoiseHeavy Equipment Hot PartsIntroduction List of Related LiteratureNameplate Emission InformationService Assistance Service Assistance TP-6843 1/13 Descriptions and Service Views Introduction EngineGenerator Set Enclosure AlternatorAccessories Carburetor HeaterOnCue Generator Management System Programmable Interface Module PIMService Views 3Optional Communications Kit Components Theory of Operation Prestart ChecklistGenerator Set Operation Exercising the Generator Set Generator Set OperationShutdowns FaultsExercise Resetting the Controller After a Fault Shutdown Fault Message ShutdownSD Condition Check5Controller Fault Messages Generator Set Operation TP-6843 1/13 VSC Generator Set Controller Control and IndicatorsVSC Controller Operation LED Indicators Controller Keypad6Autopaging Displays, Automatic Mode LCD DisplayController Power Battery ChargingChanging Settings Procedure to Change Settings7Changing Settings Setting the Exerciser Setting the Exerciser at Controller Power-upChanging the Exercise Settings Procedure to Set the Exerciser8Procedure to Set the Exerciser on the VSC Controller VSC Controller Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu CalibrationGenerator Set Information Menu Genset Run Time MenuSystem Parameters for Battery Bank Charging Genset System MenuNominal Voltage 24V 36V 48V System Voltage, VDC Setting the Exerciser Adjusting the Display ContrastDate and Time Menu Networking Information MenusNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Password PasswordRbus Information RbusRemote Devices Submenu 25Remote Devices SubmenuProgrammable Interface Module PIM Status Menu Procedure to View Event History Event LogVSC Controller Operation TP-6843 1/13 Scheduled Maintenance Scheduled MaintenanceService Schedule, 6VSG Models FuelOil Change Procedure Lubrication SystemLow Oil Pressure Shutdown Oil CheckResetting the Maintenance Timer Spark PlugsPaper Element Service Air Cleaner ServicePrecleaner Service Engine Starting Battery Cooling SystemStorage Procedure Lubricating SystemFuel System Cylinder LubricationBattery Troubleshooting Fault MessagesController Service Access IntroductionTroubleshooting Problem Possible Cause Recommended ActionAppendix a Abbreviations AbdcSysteme international d’unites TP-6843 1/13 Appendix Appendix TP-6843 1/13 Page 2012, 2013 by Kohler Co. All rights reserved