Kohler 36VDC, 6VSG, 24VDC, 48VDC manual Troubleshooting, Problem Possible Cause Recommended Action

Page 54

5.5 Troubleshooting

Figure 5-2contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections before replacing parts.

Problem

Possible Cause

Recommended Action

 

 

 

Controller

Backlight turns off after about 1 minute with no

Backlight will turn on when a button is pressed or the

display backlight

activity.

generator set starts.

is off.

 

 

 

 

 

Controller

Low or no battery voltage.

Check connections.

display is off.

 

Check generator set battery. See Figure 1-2.

 

 

 

The generator

Battery weak or dead.

Recharge or replace the battery.

set does not

 

 

Battery connections reversed or poor.

Check the connections.

crank.

 

 

 

Fault shutdown.

Check the controller display for fault messages. See

 

 

Section 2.6. Correct the fault condition and reset the

 

 

controller.

 

 

 

 

Generator set in the OFF mode.

Press the RUN button to start the engine or press AUTO

 

 

to allow remote starting.

 

 

 

The generator

Air cleaner clogged.

Clean and/or replace the air cleaner.

set cranks but

 

 

Battery weak or dead.

Recharge or replace the battery.

does not start,

 

 

starts hard,

Battery connection poor.

Clean and tighten the battery connections.

lacks power, or

 

 

Spark plug wire connection loose.

Check the spark plug wires.

operates

 

 

Low oil pressure shutdown.

Check for oil leaks. Check the oil level and add oil if

erratically.

 

 

necessary.

 

Fuel pressure insufficient.

Check the fuel supply and valves.

 

 

 

 

Engine malfunction.

Contact an authorized Kohler distributor/dealer.

 

 

 

No DC output.

Line circuit breaker in the OFF position.

Place the circuit breaker in the ON position.

 

 

 

 

Line circuit breaker tripping because of overload.

Reduce the load on the generator set.

 

 

 

 

Line circuit breaker tripping because of short

Contact an authorized Kohler distributor/dealer for

 

circuit.

service.

 

 

 

 

Rectifier has failed.

Verify that the generator is providing AC voltage.

 

 

 

Low output or

Generator set overloaded.

Reduce the load.

excessive drop

 

 

in voltage.

 

 

 

 

 

Generator set

Low oil pressure shutdown.

Check for oil leaks. Check the oil level and add oil if

stops suddenly.

 

necessary.

 

 

 

 

Out of fuel.

Check fuel supply.

 

 

 

 

Overcrank shutdown.

Reset the controller. If the overcrank fault occurs again,

 

 

contact an authorized Kohler distributor/dealer.

 

 

 

 

Auxiliary winding circuit breaker tripped.

Reset the circuit breaker (located in controller’s service

 

 

access area). Contact an authorized Kohler

 

 

distributor/dealer for service if breaker trips repeatedly.

 

 

 

 

Fault shutdown.

Check the controller display for fault messages. See

 

 

Section 2.6. Correct the fault condition and reset the

 

 

controller.

 

 

 

 

Generator set in the OFF mode.

Press the RUN button to start the engine or press AUTO

 

 

to allow remote starting.

 

 

 

 

Remote stop command received from a remote

Check the remote switch position. Check OnCue®.

 

switch, or OnCue®.

 

 

Engine malfunction.

Contact an authorized Kohler distributor/dealer.

 

 

 

Figure 5-2General Troubleshooting Chart

54 Section 5 Troubleshooting

TP-6843 1/13

Image 54
Contents VSC TP-6843 1/13aGenerator Set Identification Numbers Product Identification InformationController Identification Engine IdentificationTable of Contents Table of Contents Scheduled MaintenanceAppendix a Abbreviations Safety Precautions and Instructions BatteryAccidental Starting Engine Backfire/Flash Fire Exhaust SystemUse extreme care when handling, storing, and using fuels Fuel System Hazardous NoiseHeavy Equipment Hot PartsIntroduction List of Related LiteratureNameplate Emission InformationService Assistance Service Assistance TP-6843 1/13 Generator Set Enclosure Descriptions and Service ViewsIntroduction Engine AlternatorOnCue Generator Management System AccessoriesCarburetor Heater Programmable Interface Module PIMService Views 3Optional Communications Kit Components Prestart Checklist Generator Set OperationTheory of Operation Exercising the Generator Set Generator Set OperationFaults ExerciseShutdowns Resetting the Controller After a Fault Shutdown Fault Message ShutdownSD Condition Check5Controller Fault Messages Generator Set Operation TP-6843 1/13 Control and Indicators VSC Controller OperationVSC Generator Set Controller LED Indicators Controller Keypad6Autopaging Displays, Automatic Mode LCD DisplayChanging Settings Controller PowerBattery Charging Procedure to Change Settings7Changing Settings Changing the Exercise Settings Setting the ExerciserSetting the Exerciser at Controller Power-up Procedure to Set the Exerciser8Procedure to Set the Exerciser on the VSC Controller VSC Controller Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu CalibrationGenerator Set Information Menu Genset Run Time MenuSystem Parameters for Battery Bank Charging Genset System MenuNominal Voltage 24V 36V 48V System Voltage, VDC Setting the Exerciser Adjusting the Display ContrastDate and Time Menu Networking Information MenusNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Password PasswordRbus Information RbusRemote Devices Submenu 25Remote Devices SubmenuProgrammable Interface Module PIM Status Menu Procedure to View Event History Event LogVSC Controller Operation TP-6843 1/13 Scheduled Maintenance Scheduled MaintenanceService Schedule, 6VSG Models FuelLow Oil Pressure Shutdown Oil Change ProcedureLubrication System Oil CheckResetting the Maintenance Timer Spark PlugsAir Cleaner Service Precleaner ServicePaper Element Service Engine Starting Battery Cooling SystemFuel System Storage ProcedureLubricating System Cylinder LubricationBattery Controller Service Access TroubleshootingFault Messages IntroductionTroubleshooting Problem Possible Cause Recommended ActionAppendix a Abbreviations AbdcSysteme international d’unites TP-6843 1/13 Appendix Appendix TP-6843 1/13 Page 2012, 2013 by Kohler Co. All rights reserved