Kohler 6VSG Setting the Exerciser at Controller Power-up, Changing the Exercise Settings

Page 28

3.6 Setting the Exerciser

Set the exerciser to automatically run the generator set for 20 minutes every week or every two weeks.

3.6.1Setting the Exerciser at Controller Power-up

When battery power is connected to the controller, you will be prompted to set the date and time, and then to set the exerciser.

The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section

3.5for more detailed instructions to change settings on the VSC.

If the battery is disconnected and reconnected during generator set maintenance or service, the time, date, and exercise settings will need to be re-entered.

3.6.2Changing the Exercise Settings

This section explains how to change the exercise settings after the initial setup.

Follow the procedure below and see the flowchart in Figure 3-8to set the exercise time and date, mode, and frequency.

Procedure to Set the Exerciser

1.Press the AUTO button on the controller.

2.Press the Select button to go to the main menu. See Figure 3-9.

3.Press the down arrow button to step to the Genset System menu.

4.Press the Select button to enter the Genset system menu. See Figure 3-11.

5.Use the down arrow button to step to the Next Exercise menu. If the exerciser is not set, No Exercise Scheduled will be displayed.

6.Press and HOLD the Select button to enable editing.

7.Press the Select button. The setting flashes to show that it can be changed. For example, HR flashes to show that the hour can be changed.

8.Press the Up or Down arrow buttons to change the setting.

9.Press the Select button to save the setting and move to the next. For example, save HR setting and move to MN.

10.Repeat steps 5 through 9 to change the next item on the line until the desired settings are displayed.

11.Press Select to save after all settings have been selected. Settings will stop flashing.

12.Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended.

13.Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu.

After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency setting.

Exerciser Reset

To reset the exerciser to run at a different day and/or time or to change the exercise mode, follow the procedure in Section 3.6.2 to change the exerciser settings.

28 Section 3 VSC Controller Operation

TP-6843 1/13

Image 28
Contents VSC TP-6843 1/13aProduct Identification Information Controller IdentificationGenerator Set Identification Numbers Engine IdentificationTable of Contents Scheduled Maintenance Table of ContentsAppendix a Abbreviations Battery Safety Precautions and InstructionsAccidental Starting Engine Backfire/Flash Fire Exhaust SystemUse extreme care when handling, storing, and using fuels Fuel System Hazardous NoiseHeavy Equipment Hot PartsIntroduction List of Related LiteratureNameplate Emission InformationService Assistance Service Assistance TP-6843 1/13 Descriptions and Service Views Introduction EngineGenerator Set Enclosure AlternatorAccessories Carburetor HeaterOnCue Generator Management System Programmable Interface Module PIMService Views 3Optional Communications Kit Components Generator Set Operation Prestart ChecklistTheory of Operation Exercising the Generator Set Generator Set OperationExercise FaultsShutdowns Resetting the Controller After a Fault Shutdown Fault Message ShutdownSD Condition Check5Controller Fault Messages Generator Set Operation TP-6843 1/13 VSC Controller Operation Control and IndicatorsVSC Generator Set Controller LED Indicators Controller Keypad6Autopaging Displays, Automatic Mode LCD DisplayController Power Battery ChargingChanging Settings Procedure to Change Settings7Changing Settings Setting the Exerciser Setting the Exerciser at Controller Power-upChanging the Exercise Settings Procedure to Set the Exerciser8Procedure to Set the Exerciser on the VSC Controller VSC Controller Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu CalibrationGenerator Set Information Menu Genset Run Time MenuSystem Parameters for Battery Bank Charging Genset System MenuNominal Voltage 24V 36V 48V System Voltage, VDC Setting the Exerciser Adjusting the Display ContrastDate and Time Menu Networking Information MenusNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Password PasswordRbus Information RbusRemote Devices Submenu 25Remote Devices SubmenuProgrammable Interface Module PIM Status Menu Procedure to View Event History Event LogVSC Controller Operation TP-6843 1/13 Scheduled Maintenance Scheduled MaintenanceService Schedule, 6VSG Models FuelOil Change Procedure Lubrication SystemLow Oil Pressure Shutdown Oil CheckResetting the Maintenance Timer Spark PlugsPrecleaner Service Air Cleaner ServicePaper Element Service Engine Starting Battery Cooling SystemStorage Procedure Lubricating SystemFuel System Cylinder LubricationBattery Troubleshooting Fault MessagesController Service Access IntroductionTroubleshooting Problem Possible Cause Recommended ActionAppendix a Abbreviations AbdcSysteme international d’unites TP-6843 1/13 Appendix Appendix TP-6843 1/13 Page 2012, 2013 by Kohler Co. All rights reserved