Map. Choose alarms or events to map to this relay:

Operation: Set Up Contacts and Relays

Action. Set the System controller to respond to the change of status for an input in one of the following ways:

Map

Description/Function

 

 

Status Only

Displays the event on the Active Alarms

 

screen. Status-only events are not logged.

 

 

Minor Alarm

Activates the Warning LED and the alarm

 

beeper. It also creates an entry in the event log.

 

 

Major Alarm

Activates the Alarm LED and the alarm

 

beeper. It also creates an entry in the event log.

 

 

Remote Run/Stop

Shuts down the Modules normally, waiting for

 

delay timers.

 

 

Nonessential Lockout

Deactivates modes set as nonessential and

 

continues operation.

 

 

Immediate Shutdown

Shuts down the Modules immediately. It does

 

not wait for the blower delay or compressor

 

timers.

 

 

Output relays

Path: Main > Setup > System # > Input/Output > Output Relays

The Main Module supports up to 16 user-defined output relays. Output relays respond to internal alarms and events by changing state to notify outside devices.

Relay Out. Choose the relay number to view or modify.

Map. Choose alarms or events to map to this relay:

The first line of the map field displays the location of the event that is mapped to this relay. It can be a System, Main Module, Expansion Module 1, or Expansion Module 2 event.

The second line displays the name of the event mapped to this relay.

Any input contact and output relay available in this System can be mapped to this relay.

Note

14

NetworkAIR IR Operation, Maintenance, and Troubleshooting