Operation: Set Up Contacts and Relays
Action. Set the System controller to respond to the change of status for an input in one of the following ways:
Map | Description/Function |
|
|
Status Only | Displays the event on the Active Alarms |
| screen. |
|
|
Minor Alarm | Activates the Warning LED and the alarm |
| beeper. It also creates an entry in the event log. |
|
|
Major Alarm | Activates the Alarm LED and the alarm |
| beeper. It also creates an entry in the event log. |
|
|
Remote Run/Stop | Shuts down the Modules normally, waiting for |
| delay timers. |
|
|
Nonessential Lockout | Deactivates modes set as nonessential and |
| continues operation. |
|
|
Immediate Shutdown | Shuts down the Modules immediately. It does |
| not wait for the blower delay or compressor |
| timers. |
|
|
Output relays
Path: Main > Setup > System # > Input/Output > Output Relays
The Main Module supports up to 16
Relay Out. Choose the relay number to view or modify.
Map. Choose alarms or events to map to this relay:
•The first line of the map field displays the location of the event that is mapped to this relay. It can be a System, Main Module, Expansion Module 1, or Expansion Module 2 event.
•The second line displays the name of the event mapped to this relay.
Any input contact and output relay available in this System can be mapped to this relay.
Note
14 | NetworkAIR IR Operation, Maintenance, and Troubleshooting |