Operation: Set Up System Configuration
Building management
Path: Main > Setup > System # > System Config > Building Management
If you are using a building management system with your NetworkAIR IR
Address. The address of the Main Module on the
Baud Rate. The bus speed for the RS-485 bus.
Parity. The parity for the
Stop Bits. The stop bits for the
See the Installation Manual to wire the electrical connections to the
Sensor setup
Path: Main > Setup > System # > System Config > Sensor Setup
Specify the set of sensors the NetworkAIR IR
Temp/Hum Snsrs: Choose the set of temperature and humidity sensors the controller will use when determining the need for environmental control. The return sensors and the remote sensor string are available.
Dflt Snsrs: Choose the sensor group that the System will use when the System settings are reset to their default values.
Rmt Snsr Data: When determining the environmental controls, choose the measurement from the remote sensors for the controller to use.
•Max — Use the value reported by the remote temperature and humidity probe reporting the maximum value on the remote sensor string.
•Avg — Use the average of all of the remote temperature and humidity probe values.
NetworkAIR IR Operation, Maintenance, and Troubleshooting | 9 |