Operation: Respond to Alarms
Alarm messages and suggested actions
Displayed Alarm Message | Action Required |
|
|
Air Block Interlock Open | • Verify that the air block is in place. |
| • Confirm that the wiring connections for the air block interlock are secure. |
|
|
Air Filter Clogged | • Verify the condition of the return air filters, and replace them if required. |
| • Check the pressure drop across the filters by reviewing the System status. |
| • Ensure that the |
| • Verify that the ends of the |
| incorrectly. |
| • Verify that the correct filter is selected in the System Options menu (Path: |
| Main > Setup > System > System Config > System Options). |
|
|
Airflow Low | • Check the pressure drop across the filters, and replace the filters if necessary. |
| • Check the pressure drop across the evaporator coil on the pressures screen of |
| the display interface (Path: Main Menu > Status > [Module] > Pressures). |
| The reading should be close to the recommended coil differential pressure |
| drops indicated in the table “Coil Differential Pressure Values” on page 17. If |
| the reading is too low based on Module size and options installed, adjust the |
| blower speed. |
| • Verify the proper operation of the Variable Frequency Drive (VFD) and |
| blower motors. |
| • Verify that the VFD overload alarm is not active. |
| • Ensure that any |
| • Verify that the Mode Delay is not too short. If the Mode Delay is too short, |
| the Airflow Low alarm occurs after |
| minutes. |
|
|
Backup is Load Sharing | • A backup System is contributing to meet the room load. |
| • No action required. The backup will return to idle when the demand falls. |
|
|
Backup System Idle | • A primary System has come back online after a failover event. |
| • No action required. |
|
|
Backup System Online | • Indicates that a System failover has occurred. The backup System has come |
| online due to another online System that either failed or was commanded off. |
| A System Comm Loss is considered to be a System failure if the Comm |
| Loss Failover configuration setting is Yes (the default setting). |
| • Check the System’s event log to determine the cause of the System failure. |
|
|
Blower 1 Requires Maintenance | • Verify operation of Blower 1 and perform preventive maintenance. |
| • Reset the maintenance alarm for Blower 1 on the display interface. |
|
|
Blower 2 Requires Maintenance | • Verify operation of Blower 2 and perform preventive maintenance. |
| • Reset the maintenance alarm for Blower 2 on the display interface. |
|
|
Condensate Pump Fail | • Verify that the condensate pump circuit breaker has not been tripped. |
| • Ensure that the wiring between the float switch for the condensate pump and |
| the controller is secure. |
| • Confirm that the condensate removal lines are free of debris and are |
| unobstructed. |
| • Confirm the line voltage at the condensate pump. |
| • Ensure that the condensate float switch is moving freely and does not bind. |
| • Confirm that the condensate pump reservoir is clean and free of debris. |
| • Replace the condensate pump. |
|
|
40 | NetworkAIR IR Operation, Maintenance, and Troubleshooting |