Network Management Card: Quick Configuration
Local access to the control console
You can use a local computer that connects to the NetworkAIR IR System through the serial port on the control board to access the control console. Whenever possible access the control panel through a network connection.
The procedure requires the front door and right side (low voltage) of the electrical panel of the NetworkAIR IR
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Use the configuration cable (APC part | Network Management Card |
number |
|
port to the serial port (J2) on the |
|
controller board. The controller board is |
|
in the right compartment of the electrical |
|
panel. | Serial Port (J2) |
Do not touch components on the electrical panel, other than the serial port.
3. Run a terminal program (such as HyperTerminal) and configure the selected port for 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow control, and save the changes.
4.Press ENTER to display the User Name prompt.
5.Use apc for the user name and password.
6.See “Control console” on page 52 to finish the configuration.
NetworkAIR IR Operation, Maintenance, and Troubleshooting | 51 |