American Power Conversion Central Air Conditioning System manual Displayed Alarm Message

Models: Central Air Conditioning System

1 84
Download 84 pages 23.05 Kb
Page 48
Image 48

Operation: Respond to Alarms

Displayed Alarm Message

Action Required

 

 

Env Temperature Low

• Verify that no supply air is fed directly back into the return air.

 

• Ensure that the alarm delay is not set too low. The delay should be long

 

enough to allow the room temperature to stabilize after start-up.

 

• Verify that the temperature alarm threshold for the environmental (return or

 

remote) sensors is below the cool and reheat setpoints.

 

• Verify that the Module is configured and equipped for the reheat mode.

 

• Ensure that the reheat mode is enabled (if your Module is equipped with

 

reheat).

 

• Ensure that the reheat mode is not disabled because of an active user-defined

 

input mapped to nonessential lockout.

 

 

Fire Detected

• Follow the appropriate facility emergency protocol. NOTE: The purpose of

 

the fire sensor is to warn you of possible equipment damage. It is NOT

 

intended to provide a fire alarm system to protect the facility and the lives of

 

its occupants.

 

• Confirm that the wiring connections are secured to the wiring harness.

 

• Verify the setting of the fire detector (fire stat).

 

• Replace the fire detector (fire stat).

 

 

Fluid Coil Actuator Fail

• Verify that the connections between the actuator and the controller board are

 

correct and securely tightened.

 

• Confirm that the control voltage and signal voltage reach the actuator.

 

• Ensure that the proper Module configuration is defined for this Module,

 

especially that the coil configuration and the actuator type are correct.

 

• Replace the Coil Fluid Actuator.

 

 

Group Configuration Invalid

• Check that the # Systems setting (Path: Main > Setup > Group > Group

 

Config) agrees with the actual number of Systems connected to the Group.

 

Increase this setting to match the number of connected Systems.

 

 

Group Configuration Conflict

• Verify the Group configuration settings (Path: Main > Setup > Group) are

 

correct. The Group detected one or more Systems in the Group to have

 

different Group configuration settings and changed that System’s settings.

 

 

Group Fatal Fire Shutdown

• Check the Systems in this Group for fire alarms. The Group Fatal Fire

 

Shutdown occurs only when the Group Fire Alarm configuration setting

 

(Path: Main > Setup > Group Config > Grp Fire Alrm) is On. While the

 

fire alarm is active, the Group will remain shut down.

 

 

Group Fatal Smoke Shutdown

• Check the Systems in this Group for smoke alarms. The Group Fatal Smoke

 

Shutdown occurs only when the Group Smoke Alarm configuration setting

 

(Path: Main > Setup > Group Config > Grp Smoke Alrm) is On. While

 

the smoke alarm is active, the Group will remain shut down.

 

 

Heater Requires Maintenance

• Verify the operation of the heater and perform preventive maintenance.

 

• Reset the maintenance alarm on the display interface for the heater.

 

 

Humidifier Current High

• Verify that the proper voltage is applied to the humidifier cylinder.

 

• Confirm that the line voltage connections to the cylinder are secure and

 

correct.

 

• Ensure that the humidifier water supply has not been conditioned.

 

Conditioning can increase the water conductivity.

 

• Check the humidifier cylinder for mineral buildup that bridges the electrodes.

 

• Check the fill and drain valves for leaks.

 

 

42

NetworkAIR IR Operation, Maintenance, and Troubleshooting

Page 48
Image 48
American Power Conversion Central Air Conditioning System Displayed Alarm Message, Action Required, Env Temperature Low