Troubleshooting:
Problem | Possible Cause | Corrective Action |
|
|
|
Humidifier | • Water supply is not on. | • Turn on the supply. |
inoperative | • Electrical connections are | • Tighten all electrical connections. |
| loose. |
|
| • Humidifier fuse is open. | • Check for short circuits, and replace blown fuses. |
| • Relative humidity is above | • No action needed. |
| the setpoint. |
|
|
|
|
Reheat elements | • Overheat switch is actuated. | • Reset and check for operation. |
inoperative | • A fuse is open. | • Check for short circuit. |
| • The thermostat is set too low. | • Adjust thermostat to required temperature. |
| • The thermal fuse in the | • Replace thermal fuse. |
| heater is open. |
|
|
|
|
Water | • Insufficient air quantity over | • Check for correct airflow and clean filters. |
| the cooling coil. |
|
| • Dirty coil. | • Clean the coil. |
| • Excessive airflow. | • Reduce airflow to specifications. |
| • Blocked drain pan or trap. | • Clean the drain pan and trap. |
|
|
|
Module is receiving | • Remote shutdown enabled. | • Disable remote shutdown. |
power, but will not |
|
|
operate |
|
|
|
|
|
NetworkAIR IR Operation, Maintenance, and Troubleshooting | 69 |