American Power Conversion Central Air Conditioning System manual Problem, Possible Cause

Models: Central Air Conditioning System

1 84
Download 84 pages 23.05 Kb
Page 74
Image 74
Airflow too high

Troubleshooting: Semi-Annual Preventive Maintenance

Problem

Possible Cause

Corrective Action

Airflow too high

• External static pressure may

 

be too low.

Check the evaporator coil pressure drop through the display interface. Pressure should match the recommended pressure drops indicated on the chart based on Module size. If the pressure drop is above the recommended settings, decrease the blower speed until the pressure drop matches the recommended setting. See “Calibrate airflow manually” on page 17.

Temperature control

• Cooling and reheat settings

not precise enough

are not close enough.

 

• Reheat PID loop is not

 

properly tuned.

 

• SCR controller is not

 

working.

 

• The mode of operation is

 

turned off.

 

Non-essential lockout has

 

been activated by a user-

 

defined input with the

 

equipment.

 

• Return air temperature is

 

reading incorrectly.

Check setpoints for cooling and heating as well as deadbands.

Tune the PID loop for accurate reheat operation.

Confirm the operation of the SCR controller.

Check to verify that the proper modes of operation, cooling, and reheat are activated. A Module must have specific options installed to allow all modes of operation to be active.

Review event log to see if this alarm input has been activated.

Return air is not coming from the common space and may be influenced by a close heat source or a discharge air duct affecting return air temperatures. Try to eliminate the hot or cold air stream or relocate the sensor for better room temperature readings.

Humidification

• Check the setpoints for

control is not

humidification and

precise enough

dehumidification.

 

• Humidifier may not be

 

operating correctly.

 

• The mode of operation is

 

turned off.

 

Non-essential mode input

 

has been activated by

 

customer interface with

 

equipment.

 

• The room is not properly

 

sealed internally to maintain

 

vapor pressure in the

 

controlled space.

Verify that the setpoints are not too far apart. Typical setpoint between humidification and dehumidification is 10%.

Verify humidification operation. Ensure that there are no humidifier alarms that could impede the humidification process.

Ensure that the proper modes of operation, humidification and dehumidification, are activated. A Module must have specific options installed to allow all modes of operation to be active.

Review the event log to see if this alarm input has been activated.

The room must have an adequate vapor barrier installed to maintain humidification and dehumidification setpoints. The vapor barrier is inadequate if humidity in the controlled space changes based on influences from the surrounding air outside the controlled space.

68

NetworkAIR IR Operation, Maintenance, and Troubleshooting

Page 74
Image 74
American Power Conversion Central Air Conditioning System Problem, Possible Cause, Corrective Action, Airflow too high