Respond to Alarms
When an alarm is triggered, the Main Module alerts you through the display by the following methods:
•Alarm beeper
•Major or Minor Alarm LED
•Active alarm screen
•Alarm/Event log
Major or minor alarm LEDs
When an alarm is triggered, the Check Log LED and either the Minor Alarm LED or the Major Alarm LED activates. The Major and Minor Alarm LEDs cannot be deactivated manually; the alarm condition must be cleared to deactivate them.
Control beeper
Path: Main > Respond to Alarms
An active alarm creates a beeping sound from the display. This sound continues until you view the Respond to Alarms menu.
Beeper. To disable the beeper for all future alarms, set the Beeper setting to Disabled.
Beeper Volume. Set the volume of the beeper and
View active alarms
Path: Main > Respond to Alarms > View Active Alarms
The Active Alarms screen also appears on the scrolling status screens. It provides the number of the alarm (e.g. 1 of 2), a description of the condition, and a
See “Entire Log” on page 37 for more information on the alarm/event details screens.