Operation: Respond to Alarms

Displayed Alarm Message

Action Required

 

 

System Failure

• After correcting the cause of the system failure, perform a Reset System

 

Failure command (Path: Main > Respond to Alarms > Reset Sys Failure).

 

 

System Fire Detected

• Follow the appropriate facility emergency protocol. NOTE: The purpose of

 

the fire sensor is to warn you of possible equipment damage. It is NOT

 

intended to provide a fire alarm system to protect the facility and the lives of

 

its occupants.

 

• See “Fire Detected” on page 42 for the appropriate alarm actions.

 

 

System Off

• Turn on power to the System (Path: Main > On/Off).

 

 

System Smoke Detected

• Check the Modules in the System for Smoke Detected alarms.

 

• Follow the appropriate facility emergency protocol. NOTE: The purpose of

 

the smoke sensor is to warn you of possible equipment damage. It is NOT

 

intended to provide a smoke alarm system to protect the facility and the lives

 

of its occupants.

 

• See “Smoke Detected” on page 44 for the appropriate alarm actions.

 

 

VFD # 1 Requires Maintenance

• Verify the operation of VFD # 1 and perform preventive maintenance.

 

• Reset the maintenance alarm for VFD #1 on the display interface.

 

 

VFD # 2 Requires Maintenance

• Verify the operation of VFD # 2 and perform preventive maintenance.

 

• Reset the maintenance alarm for VFD # 2 on the display interface.

 

 

Water Detected

• Determine the source of the leak, and repair it.

 

• Confirm that the water detector is not short-circuited to metal and ensure that

 

there is not debris or soldering on the rope component of the water detector

 

that could be providing false detection.

 

• Ensure that the water detector is properly mounted and secured to the bottom

 

of the Module or the floor.

 

• Confirm that the wiring connections are secure.

 

• Replace the water detector.

 

 

NetworkAIR IR Operation, Maintenance, and Troubleshooting