Operation: View Status Readings
About Module. View identifying information that is helpful when obtaining service:
•Manufacturer Name
•Model Number
•Date of Manufacture
•Serial Number
•Firmware Revision
•Hardware Revision
Humidifier Status. View the humidifier output, current drawn by the humidifier, and the conductivity of the water in the humidifier cylinder in this Module.
Water Temps. View the coil fluid inlet temperatures for the coolant and hot water supplies (if applicable).
Blower [#] Status. View the status of blower 1 and blower 2 and the variable frequency drives that control the blowers.
Compressor Status. View the suction and discharge pressures for the Module and the operating (on or off) status of each compressor. The condenser fluid valve position is also displayed on this screen.
. System status
Path: Main > Status > System #
The System status screens include information about the entire System.
Temp & Humidity. View the average temperature and humidity readings at the sensors in this System (same as the Temp & Humidity scrolling status screen).
Return Sensors View the average temperature and humidity at the return sensors for this System.
Remote Sensors View the minimum temperature, average temperature, average humidity, and maximum temperature for the remote sensor probes.
Demands. View the percentage of output required of a mode to maintain its setpoint in the room.
Cool/Dehumidify View the cool mode and dehumidify mode demands (%) and the actual output. The actual reading is combined for the cool and dehumidify modes. The actual reading for the mode with the largest demand is displayed.
Reheat Demand View the status (On/Off) of the reheat mode as well as its percentage of demanded output. The On/Off status for reheat is displayed only for Modules equipped with steam, hot water, or hot gas reheat.
Humidify Demand View the actual and demanded output for the humidify mode.