Using the Avaya Remote Supervisor Adapter

Viewing system health summary

Figure 27: System health temperature thresholds

The reported temperatures for system components are measured in the following ranges:

Warning Reset: If the temperature returns to a value below the warning reset value, the RSA assumes that the temperature has returned to normal and does not generate any further alerts.

Warning: If the temperature reaches or exceeds the value specified for a warning, an alert is generated.

Soft Shutdown: When the temperature reaches or exceeds the value specified for a soft shutdown, a second temperature alert is sent and the RSA begins the shutdown of the S8500 Media Server. The shutdown will be an orderly operating-system shutdown. The S8500 Media Server turns itself off when the shutdown completes.

Hard Shutdown: When the temperature reaches or exceeds the value specified for a hard shutdown, the S8500 Media Server immediately shuts down. The RSA sends out an alarm to the configured alert recipients.

Voltage thresholds

The RSA sends an alert if any monitored power source voltage falls outside the specified operational ranges.

The voltages section displays the values RSA reacts to when reached or exceeded (see Figure 28, System health voltage, on page 55). The values are not programable and cannot be changed.

Figure 28: System health voltage

Avaya Remote Supervisor Adapter User Guide

55

November 2003

 

Page 55
Image 55