D9412GV2/D7412GV2 Operation and Installation Guide 9.0 Off-Board Points

Figure 16: Connecting D8128D OctoPOPITs to the D9412GV2

1

5

2122

Reset Pin

Disable All Except Battery

Charging And Programming

PERIPHERAL DEVICE CONNECTIONS

RED

POWER +

32

YELLOW

DATA BUS A

31

GREEN

DATA BUS B

30

BLACK

COMMON

29

 

 

 

N.F.P.A.

ZONEX OUT 1

28

Style 3.5

 

 

Signaling

 

 

Line

 

27

Circuits

ZONEX IN 1

 

ZONEX OUT 2

26

 

ZONEX IN 2

25

 

ZONEX POWER +

24

 

ZONEX COMMON

23

Point 8

D5200/D5360

S3 Option

PROG CONN

Closed = 1KEOL

 

Normal Operation

 

Open =AB-12 UL

 

Bell Box 220 K

 

GRN

 

2

3

2

4

6

6

7

11

8

9

8

10

12

6

6

1 - Zonex Bus 1, Switch 1 ON (Points 9 to 72)

8 -

Bus 2

2 -

Bus 1

 

9 - First address on Zonex Bus 2

3 - First address on Zonex Bus 1

10

- Last address on Zonex Bus 2

4 - Last address on Zonex Bus 1

11

- Zonex Bus 2, Switch 1 OFF (Points 193 to

5 - Zonex Bus 1, Switch 1

OFF (Points 73 to 127)

 

240)

6 -

Sensor loops

 

12

- On-board points

7 - Zonex Bus 2, Switch 1

ON (Points 129 to 192)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 41 for information about making these switch settings.

44

Bosch Security Systems, Inc. 5/05 F01U003641B