UL Smoke Detector Compatibility (P/N: 33284) for

D9412GV2/D7412GV2 Operation and Installation Guide Appendix A: System Wiring Diagrams, Issue A

Figure 38: D7412GV2, Input Points and Peripheral Devices

+-

D130

CLASS 2 TRANSFORMER

16.5VAC 40 VA 60 Hz Model D1640

Internally Fused - Do Not short Requires Unswitched Outlet

Do Not Share With Other Equipment

+ AUX POWER

BATTERY NEGATIVE ONLY

Maximum Charging

Current 1.4 Amps.

BATTERY POSITIVE ONLY

RELAY A

PROGRAMMABLE

ALARM OUTPUTS

 

 

Terminals

RELAY B

7 & 8

 

Requires Optional

Model D136 Relay

RELAY C In ALT ALARM

& SW AUX

COMMON

EARTH GROUND

GROUND FAULT DETECT

Enabled

Disabled

 

PHONE

ON when

RED

communicating

 

LED

OFF when idle

 

PHONE LINE SEIZED

TIP

TELCO CORD

RING

 

 

MODEL D161

D7412GV2

 

 

VOLTAGE RANGES

 

 

Open

3.7 - 5.0 VDC

 

 

Normal

2.0 - 3.0 VDC

 

 

Short

0.0 - 1.3 VDC

Point 1 Point 2

Point 3 Point 4

Point 5 Point 6

Point 7 Point 8

11

12

13

14

15

16

17

18

19

20

21

22

PHONE LINE

SEIZED

TIP

 

 

 

 

 

 

RING

TELCO

D125B

Sw. Aux Pwr

1

 

Zone B

2

D129

Zone A

3

 

Pnl Common

4

 

Pnl Common

5

 

Loop B-

6

 

Loop A-

7

 

Loop B+

8

 

Loop A+

9

 

Earth Ground

10

 

P105BL

P105F

Loop B+

1

Loop B-

2

Loop B-

3

Loop B+

4

Zone B

5

Aux Power

6

Earth Ground

7

Common

8

Zone A

9

Loop A+

10

Loop A-

11

Loop A-

12

Loop A+

13

1 - (Optional): For 24 V applications, use a UL Listed

3 -

P105 1 kEOLR (P/N: 14-03130-004):

24 VDC power supply with a D130 Relay Module.

 

Suitable for non-powered initiating and

Refer to the D130 Installation Instructions

 

supervisory devices such as pull stations, heat

(P/N: 74-06262-000) for correct wiring

 

sensors, and valve tampers.

requirements.

4-

P105BL1 1kEOLR (P/N: 14-0130-004): For

2 - To UL Listed two-wire smoke detectors. Refer to

 

typical burglar alarm applications.

the 9000/G/GV2 Series Technical Service Note:

5 -

D129 provides optional Waterflow Retard

 

UL Smoke Detector Compatibility (P/N: 33284) for

feature. Not suitable for two-wire smoke

a listing of compatible two-wire smoke detectors.

detectors. (Note: Use Zero Retard except for

 

 

waterflow devices.)

All external connections except Terminal 5 (battery positive) are power limited.

68

Bosch Security Systems, Inc. 5/05 F01U003641B