D9412GV2/D7412GV2 Operation and Installation Guide 9.0 Off-Board Points

Figure 19: D8128D OctoPOPIT Sensor Loops

 

 

1

 

COM IN OUT+12V P1 COM P2

P3 COM P4

P5 COM P6

P7 COM P8

2

3

4

5

1 - D8128D OctoPOPIT

2 - To control panel

3 - To additional OctoPOPIT sensor loops

4 - OctoPOPIT sensor loops

5 - 1 kEOL resistor (P/N: P105BL, package of eight)

9.5Testing Off-Board Points

Use the Service Walk Test to test off-board points. Refer to the D9412GV2/D7412GV2/D7212GV2 Installation and Troubleshooting Quick Reference Guide (P/N: F01U003638) for instructions. Test to ensure that all off-board points operate properly.

Walk Test and Service Walk Test Do Not Show Extra Points: If the point assignment switches on a POPIT or OctoPOPIT are set incorrectly, missing and extra points can occur. If the same point number is assigned to two or more POPITs or OctoPOPITs, none of the points with that number test correctly. Refer to Section 9.1 Point (Zonex) Bus: D9412GV2 Terminals and D7412GV2 Terminals on page 34.