Bosch Appliances D9412GV2 12.6SDI Address, DX4020i DIP Switch Settings, Supervision, SDI Devices

Models: D9412GV2

1 74
Download 74 pages 9.34 Kb
Page 59
Image 59
Figure 27: DX4020i DIP Switch Settings

D9412GV2/D7412GV2 Operation and Installation Guide 12.0

SDI Devices

 

 

Figure 27: DX4020i DIP Switch Settings

2. Connect D9133DC to Com Port 1 or Com Port 2

on the PC. The D9133DC has a DB-9 female serial

connector. A null-modem cable must be purchased

1

P3

2 12.5.3 Supervision12.6SDI Address 88

LED

ENABLE

Rx Tx

Tx Rx

BUS

SER

 

P2

P6

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

DB9 GND

 

 

 

 

 

 

ENABLE

ON

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

1

2

4

8

16

32

64

128

4

separately to connect the D9133DC to a PC.

3. Using 0.8 mm (22 AWG) or 1.2 mm (18 AWG)

wire, connect the D9133DC SDI terminals (SDI

PWR, SDI A, SDI B, and SDI COM) to the

control panel’s SDI terminals (Terminals 29 to 32).

To send or receive the control panel’s program, place the Reset Pin in the Locked or Unlocked position.

Locking the Reset Pin when programming the control panel improves the uploading and downloading times.

1 - Address DIP switches

2 - OFF position

3 - ON position

4 - SDI Address 80 switch settings

12.5.3 Supervision

Supervision of the serial interface module is available through programming. Supervision is not required to use a DX4010i or a D9133.

If supervised, and the serial interface module does not respond to control panel supervision polls, the control panel sends an SDI Failure Report to the receiver. If it fails to communicate with the DX4010i or the D9133, SERVC SDI 80 displays at the keypad. The SDI Failure Report includes the address of the troubled module indicating which module needs service.

12.6SDI Address 88

SDI Address 88 is available with the D9412GV2 and D7412GV2 Control Panels and is used for several different applications. When using SDI Address 88, connect only one listed device at a time.

12.6.1D9133DC Direct Connect Programming Module

Use the D9133DC Direct Connect Programming Module to handle local programming of the D9412GV2 and D7412GV2 Control Panels. In addition, the D9133DC allows diagnostic and history retrieval. D9133DC is not UL Listed.

Connecting the D9133DC

1.Configure D9133DC for SDI Address 88. To program the control panel when the reset pin is in the unlocked position, program Enable SDI RPS to Yes in the GV2AUX handler.

Used as an External Modem

The D9133DC can operate as an external modem when using Remote Programming Software (RPS) with the control panel. Refer to the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636) for programming details.

12.6.2 Network Interface Modules

The Bosch Security Systems DX4020 Network Interface Module and D9133TTL-E Network Interface Module are four-wire powered SDI devices that provide connection for two-way communication over Ethernet networks to D9412GV2 and D7412GV2.

For programming information on enhanced communications, refer to the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636).

The DX4020 can be installed up to 305 m (1000 ft) from the control panel using 0.8 mm (22 AWG) wire.

The D9133TTL-E can be installed up to 305 m (1000 ft) from the control panel using 1.2 mm (18 AWG) wire.