D9412GV2/D7412GV2 Operation and Installation Guide 4.0 Installation
4.6Completing the Installation
If not already complete, make the earth ground connection to Terminal 10 and lock the reset pin in the closed position.
4.6.1Charging the Battery
Connect the battery, then the transformer to allow the control panel to charge the battery while you complete the installation. Refer to Section 5.0 Power Supply on page 20 for instructions.
If the control panel fails any test, the buzzer continues sounding and a System Trouble message appears at the keypads. Refer to Problems Found during Self Diagnostics in the D9412GV2/D7412GV2/D7212GV2 Installation and Troubleshooting Quick Reference Guide (P/N: F01U003638) for a description of each system trouble message.
Touch Terminal 10 First: If the
Avoid electrostatic discharge. Always touch Terminal 10, the earth ground connection, before beginning work on the control panel.
If the control panel receives an electrostatic discharge, it might generate Watchdog Reset and Param Fail events. Refer to Watchdog Reset Reports in the D9412GV2/7412G/D7212GV2 Installation and Troubleshooting Quick Reference Guide
P/N: F01U003638) for a description of these events.
4.6.2Installing and Wiring Detection Devices
Install and wire detection devices and keypads at their locations throughout the premises. Do not connect the control panel yet.
Section 8.0
Instructions for wiring the
4.6.3Installing Modules and Relays
1.Power down the unit by unplugging the transformer and disconnecting the battery.
Always power down the unit when installing modules or relays, or when making wiring connections to the control panel.
2.Install and wire any modules required for the installation as described in the module’s installation instructions.
Instructions for the D8125 POPEX Module, D8128D OctoPOPIT Module, D8129 OctoRelay Module, D811 Arm Status Relay Module, and D928 Dual Phone Line Switcher appear in this guide.
Refer to Section 9.0
3.If using the power outputs at Terminals 7 or 8, install a D136 relay in the appropriate sockets. Refer to Section Programmable Power Output Terminals 6, 7, and 8 on page 25 for instructions.
4.6.4Connecting the On-board Points and Keypads
Connect the
4.6.5Powering Up
Reconnect the battery, then plug in the transformer. The buzzer sounds for 2 seconds when the control panel is powered up. Leave the reset pin in the locked position.
Yellow Charging Status LED Remains Lit: If the yellow charging status LED remains lit after five minutes of powering up the control panel, either the battery is deeply discharged or too many powered devices were connected to the control panel. Combined continuous current draw for Terminals 3, 8, 24, and 32, and the accessory connector cannot exceed
1.4A. Refer to Section 6.0 Power Outputs on page 25 for help.
18 | Bosch Security Systems, Inc. 5/05 F01U003641B |