3.0Overview

D9412GV2/D7412GV2 Operation and Installation Guide 3.0 Overview

3.0Overview

3.1Configuration and Parts

Figure 1: System Configuration

D9210B Modules can be used for access control.

Each D8128D OctoPOPIT combines eight POPIT points in one module.

D8129 OctoRelay provides alarm and auxiliary relay output.

(Other functions available.)

DX4020 allows communciation over a Local or Wide Area Network (LAN/WAN).

D8125, D8125INV, or D8125MUX Interface used for point expansion.

Control

Panel

On-Board Points

1 to 8

D928 Module allows the control panel to monitor two phone lines.

Use keypads or keyswitches to arm the control

panel by area. Each control panel can have up to eight areas. Each area can have its own account number or areas can be grouped together with a common account number. Points of protection are assigned to areas.

D8132 Modules (two 12 VDC, 7Ah batteries) provide additional power for keypads and other powered devices.

D9131A Module connects to a parallel printer to print the event log.

 

Table 2:

GV2 Series Control Panel Differences

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

D9412GV2

D7412GV2

D7212GV2

 

 

 

 

 

 

 

 

 

Access Control

Yes - 8 doors

 

Yes - 2 doors

 

No

 

 

Arm/Disarm Passcodes

249

 

99

 

99

 

 

Cards/Tokens

 

996

 

396

 

N/A

 

 

Passcode-Protected

16

 

4

 

4

 

 

Custom Functions

 

 

 

 

 

 

 

 

 

 

 

Number of Printers

3

 

1

 

1

 

 

Number of Points

246

 

75

 

40

 

 

 

 

 

 

 

 

 

 

Number of Relays

128

 

64

 

24

 

 

Number of Areas

8

 

8

 

4

 

 

 

 

 

 

 

 

 

 