D9412GV2/D7412GV2 Operation and Installation Guide 4.0 Installation

4.4Installing the Control Panel

1.Place the control panel over the inside back of the enclosure, aligning the large rectangular openings of the mounting skirt with the mounting hooks of the enclosure. Slide the control panel down so that it hangs on the hooks. Refer to Figure 2, Item 2 on page 15.

2.Remove the tape from the #6 x 1/4-in. screw in the mounting tab on the control panel. The screw passes through the mounting tab and into the skirt mounting hole in the enclosure. Tighten the screw to secure the control panel in the enclosure.

3.Connect earth ground to the control panel before making any other connections. Refer to Section 4.5 Connecting Earth Ground.

4.5Connecting Earth Ground

4.5.1Terminal 10

To help prevent damage from electrostatic charges or other transient electrical surges, connect the system to earth ground at Terminal 10 before making other connections. Recommended earth ground references are a grounding rod or a cold water pipe.

Warning:

Do not use telephone or electrical ground for the earth ground connection. Use

1.8mm (14 AWG) to 1.5 mm (16 AWG) wire when making the connection.

Do not connect other control panel

If a ground fault condition occurs, the keypads display SERVC GND FAULT and the control panel transmits a GROUND FAULT TROUBLE, AREA 1

(Modem IIIa2 format only).

When the control panel recognizes that the ground fault condition is corrected, and remains corrected for between 5 to 45 consecutive seconds, a Restoral Report is sent.

The D9412GV2 and D7412GV2 Control Panels log and print a Ground Fault event as a Trouble Point 256 if communicating in Modem IIIa2 format. If communicating in BFSK format, the control panels generate an Alarm Zone 5 event.

Figure 3: Ground Fault Detection

1

2

GROUND FAULT DETECT

terminals to earth ground.

4.5.2Ground Fault Detect Enable

• A ground fault is a circuit impedance to earth

ground. The control panel has a ground fault

detection circuit that, when enabled, detects

ground faults on Terminals 1 to 9 and 11 to 32.

The control panel also detects and annunciates

ground faults on any device connected to it.

3

Enabled S4

Disabled

ON when

RED PHONE communicating

LED OFF when idle

 

PHONE LINE SEIZED

TIP

TELCO CORD

RING

 

 

MODEL D161

• To enable ground fault detection, the Ground Fault

Detect Enable jumper (S4) (Figure 3) must be

locked (closed) and a non-zero value must be

entered in the Area 5 Silent Alarm Relay. When

jumper S4 is in the unlocked (open) position, the

control panel does not detect ground fault

conditions.

1 - With S4 closed, control panel detects ground faults.

2 - With S4 open, control panel does not detect ground faults.

3 - S4, Ground fault detect enable.

16

Bosch Security Systems, Inc. 5/05 F01U003641B

Page 16
Image 16
Bosch Appliances D9412GV2 manual Installing the Control Panel, Connecting Earth Ground, Terminal

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.