9C300-1 Environmental Module Operation

System Humidity

The 9C300-1 Environmental Module monitors the non-condensing humidity level of the MMAC-Plus. The results of the monitoring are available to the network manager via LCD, as well as local and remote management. The humidity levels are displayed as shown in Table 3-2.

Table 3-2. System Humidity

Humidity

LCD Display

 

 

 

 

0–45%

STATIC RISK

 

 

46–94%

NORM (normal)

 

 

95% and above

MOIST

 

 

System Voltages

The 9C300-1 Environmental Module monitors specific system power parameters to ensure that they are within acceptable limits. The power parameters monitored from the backplane are the 48 volt DC System Power Bus and the INB Termination Power Bus. The power parameter monitored within the Environmental Module is the 12 volt internal line. The results of the monitoring are available to the network manager via LCD, as well as local and remote management. Voltages above or below the acceptable voltage limits cause an alarm to be sent to the network manager. Table 3-3summarizes these acceptable voltage limits.

Table 3-3. Acceptable Voltage Limits

Description

Acceptable Voltage Limits

 

 

 

 

48 volt DC System Power Bus

From 40 volts to 59 volts

 

 

INB Termination Power Bus

From 3.1 volts to 5 volts

 

 

12 volt internal line

From 11 volts to 13 volts

 

 

Internal Operating Temperature

The 9C300-1 Environmental Module monitors its own internal operating temperature by comparing its current temperature to the ambient temperature and programmed rise temperatures to determine current temperature status. If the temperature of the Environmental Module exceeds normal operating limits, an alarm is sent to the network manager. In addition, if the ambient temperature sensor fails, pre-established temperature ranges have been programmed to ensure proper internal temperature monitoring.

3-4