5-8 Compaq R6000 Series UPS Operation and Reference Guide
Installing New Batteries
1.Make sure the manual Bypass switch at the rear of the UPS is set to Bypass.
2.Slide in the new battery packs.
3.Remove the connector covers from the new batteries and replace the screw used to retain the connector cover in the battery housing. Place the connector covers on the used batteries, using the screws in the used battery housing.
4.Attach the battery connector cables to the new batteries.
5.
6.For the Compaq R6000 UPS (and any connected ERM’s), place the battery circuit breaker in the ON position.
7.Reattach the lower front bezel to the UPS chassis using the captive screws at the sides.
8.Reset the manual Bypass switch at the rear of the UPS to the Normal position.
9. After installing the new batteries, press the Test/Reset Alarm button ( ) to initiate a
NOTE: When