6-6Compaq R6000 UPS Series Operation and Reference Guide

Caution Audible Alarm

Table 6-6

Caution Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

 

 

 

 

Caution

Beeps every five

On battery

Prepare for UPS shutdown.

 

seconds

 

 

 

 

 

 

 

 

Load is greater than

Check manual Bypass

 

 

105%, and the manual

switch on back of UPS. Turn

 

 

Bypass switch is turned

to Normal position. Reduce

 

 

to Bypass position.

load.

 

 

 

 

 

 

Ambient over-

Check air intake is not

 

 

temperature

blocked and ambient room

 

 

 

temperature is correct. If the

 

 

 

problem still exists, contact

 

 

 

an authorized service

 

 

 

provider.

 

 

 

 

 

 

Button is still being held

Let go of button. Make sure

 

 

after action is

the button travels freely, or

 

 

completed.

is not lodged.

 

 

 

 

 

 

The UPS performs a

Turn off the UPS and call an

 

 

self-test and detects a

authorized service provider.

 

 

memory location error.

 

Site-wiring fault. (Only if the site-wiring is enabled.)

Use the Front Panel controls and LCD display to examine information on the warning. If necessary, contact a licensed electrician to check input wiring, or contact an authorized service provider.

A self-test fails, indicated on the LCD display

Shut off Mains, wait until UPS shuts down, then turn breaker back ON and test again. If self-test fails again, contact an authorized service provider.

continued

Page 91
Image 91
Compaq manual 6Compaq R6000 UPS Series Operation and Reference Guide