Troubleshooting 6-3

Shutdown within 30 seconds Audible Alarm

Table 6-3

Shutdown within 30 seconds Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

 

 

 

 

Shutdown within 30

Accelerated beeping.

Over-temperature.

Check the ambient

seconds

Begins slowly, and gains

 

temperature in the

 

speed as the UPS

 

room. Refer to Appendix

 

approaches shutdown.

 

C, “Environmental

 

UPS shuts down 30 sec

 

Specifications”

 

 

 

 

after audible alarm

 

If the ambient

 

begins.

 

temperature is within

 

 

 

range and the over

 

 

 

temperature alarm is

 

 

 

chronic, contact an

 

 

 

authorized service

 

 

 

provider.

 

 

 

 

 

 

Overload.

Reduce the load. See

 

 

 

section “Connecting

 

 

 

Loads” in Chapter 2

 

 

 

 

 

 

Low battery.

Check the LCD display

 

 

 

(Meters, Battery Volts)

 

 

 

 

 

 

If a shutdown delay has

No action needed.

 

 

been programmed, the

 

 

 

accelerated alarm begins

 

 

 

before the last segment

 

 

 

shutoff.

 

 

 

 

 

 

 

Occurs during the last

No action needed.

 

 

minute of sleep timer if

 

 

 

the Sleep mode is

 

 

 

enabled.

 

 

 

 

 