Cooper Bussmann Wireless Ethernet & Device Server BU-945U-E 802.11 DSSS User Manual

Modbus TCP to RTU Gateway

The Modbus TCP to RTU Gateway allows an Ethernet Modbus/TCP Client (Master) to communicate with a serial Modbus RTU Slave.

The BU-945U-E makes this possible by internally performing the necessary protocol conversion. The conversion is always performed by the BU-945U-E which is directly connected to the Modbus serial device (i.e., only this module needs to have Modbus TCP to RTU Gateway enabled).

The above example demonstrates how a Modbus/TCP Client (Master) can connect to one or more Modbus RTU (i.e., serial) Slaves. In this example the BU-945U-E Access Point is configured with the “RS232 Modbus/TCP to RTU Gateway” enabled. Once enabled, the gateway converts the Modbus/TCP queries received from the Master into Modbus RTU queries and forwards these over the RS232 port to the Slave. When the serial response to the query arrives from the Slave, it is converted to a Modbus/TCP response and forwarded via the network to the Modbus/TCP Master. If no response was received serially by the BU-945U-E within the configured Response Timeout, the BU-945U-E will initiate a number of retries specified by the configured Maximum Request Retries.

The Modbus TCP to RTU Gateway may be configured to operate on either the RS 232 or RS 485 port.

Serial Menu

RS232 / RS485 Serial Port Configuration

RS232 Port

Select the desired functionality. Select either PPP, Serial Gateway or Modbus TCP to RTU

Data Rate

The serial data rate desired. Serial data rates available range from 110bps to a maximum of 115,200bps.

Data Format

The data format desired. All the standard data formats are supported.

Flow Control

Selects CTS/RTS or None

RS232 PPP Server (Only RS232)

 

Username

User name to enter to access RS-232 PPP Server.

Password

Password to access RS-232 PPP Server.

Local IP Address

Select the IP address of the PPP server. The remote device may be made visible on the Ethernet or

 

Wireless networks by either utilizing proxy-arp or routing. The proxy-arp feature may be enabled by

 

setting the Local IP address the same as the Ethernet IP Address or the Wireless IP Address. The module

 

will respond on behalf of the remote device, making it seem like the device is present on the configured

 

network. Alternatively, if the IP address selected is not the same as the Ethernet or Wireless IP address,

 

routing is used to pass data to the Ethernet and Wireless ports.

Remote Device IP Address

Select the IP address of the remote device. Ensure this address is not the same as any other device on

 

the Ethernet or Wireless networks.

46

www.cooperbussmann.com/BussmannWirelessResources

3A1582Rev1.6

Page 46
Image 46
Cooper Bussmann BU-945U-E 802.11 DSSS user manual Modbus TCP to RTU Gateway, Serial Menu