Cooper Bussmann BU-945U-E 802.11 DSSS user manual Multicast Pipe Manager

Models: BU-945U-E 802.11 DSSS

1 82
Download 82 pages 13.84 Kb
Page 47
Image 47

Cooper Bussmann Wireless Ethernet & Device Server BU-945U-E 802.11 DSSS User Manual

RS232 / RS485 Serial Gateway

 

 

Serial Gateway Mode

Server

Module will wait for a connection to be initiated by a remote Client.

 

Client

Module will automatically attempt to connect to the specified remote server.

 

Multicast

Allows point to multi-point serial transfer. All members of the group will receive serial

 

 

transmissions made by any other member of the Multicast group.

Modbus

Allows a serial Modbus RTU Client (Master) to connect with a single Ethernet Modbus TCP Server (Slave)

Character Timeout

Enter the maximum delay (in msec) between received serial characters before packet is sent via network.

Packet Size

The number of received bytes that will be buffered before a packet is sent via the network.

Listen Port (Server)

Server Only. Enter the TCP port number on which the server must listen for incoming connections.

 

The standard TELNET port is 23.

Remote Device Port (Client)

Client only. Enter the TCP port number of the remote server

 

(i.e., the remote port to automatically connect to).

Remote Device IP Address (Client)

Client only. Enter the IP Address of the remote server

 

(i.e., the remote IP Address to automatically connect to).

Multicast Group Port

Enter the UDP port number that all members of the group will use (i.e., all group members should

 

use the same port number).

Multicast Group IP

Enter a valid Multicast IP Address identifying the group (i.e., all group members should use the same

 

Multicast Group IP Address). Valid Multicast IP Addresses are in the range

 

224.0.1.0 to 238.255.255.255.

Modbus Server Port

This is the Server Port of the local server that a remote client will connect to.

Modbus Server IP Address

This is the IP Address of the local server that a remote Client will connect to.

RS232 / RS485 Modbus TCP / RTU Converter

 

Modbus Server TCP Port

Port number used for the Modbus TCP – Standard port is 502.

Pauses Between Requests

Enter the delay between serial request retries in milliseconds

Response Timeout

Enter the serial response timeout in milliseconds – a serial retry will be sent if a response is

 

not received within this timeout.

Connection Timeout

Enter the TCP connection timeout in seconds – if no Modbus/TCP data is received within this

 

timeout then the TCP connection will be dropped. Set this field to zero for no timeout.

Maximum Request Retries

Enter the maximum number of request retries performed serially.

Maximum Connections

Enter the maximum number of simultaneous TCP connections to the server allowed.

Multicast Pipe Manager

Previously it has been difficult to connect a single TCP device, i.e., a Scada / DCS system to multiple remote multicast serial devices.

Multicast Pipe allows this type of connection.

Example: A Scada system that needs to communicate with multiple remote serial devices. A modem can be placed at each remote location and connected serially to each device. A multicast pipe is configured to communicate with all devices using a multicast address and port,

i.e., 224.0.1.1:5000.

The Scada then communicates with the remotes via the IP address of the Multicast Manager and the port selected in the configuration, i.e., 5001.

3A1582Rev1.6

www.cooperbussmann.com/BussmannWirelessResources

47

Page 47
Image 47
Cooper Bussmann BU-945U-E 802.11 DSSS user manual Multicast Pipe Manager