Eclipse Combustion 5600 DIP Switch Selection, Modulation & Purge DIP Switch Settings

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 12
Image 12

DIP Switch Selection

3

INTRODUCTION

DIP Switch Location

DIP Switch Access

No Purge

DIP Switch Settings

Modulation & Purge DIP Switch Settings

This section details the location, selection and description of the Veri-Flame DIP switches, which allow for sequence and timing functions as well as sys- tem configuration.

Caution

To avoid electric shock, shut off the power supply when installing or removing any control device. Flame monitoring systems must be installed by a qualified, licensed technician.

All of the DIP switches are located in the back of each Veri-Flame unit (see Fig- ure 3.1 on page 13, or the photograph on page 8).

To gain access to the DIP switches, the Veri-Flame must be separated from the back box (for visual reference, please refer to “Dimensions” on page 10). This separation will expose the DIP switches on the back of the Veri-Flame unit.

No Purge models of the Veri-Flame only use three of the eight DIP switches, as shown in the labels in Figure 3.2 on page 13. They are as follows:

SW1: Recycling mode selection (On =Recycling; Off =Non-recycling)

SW2:Pilot selection (On=Intermittent,where pilot remains on during burner cycle; Off =Interrupted, where pilot valve closes after main burner is established).

SW3: Trial-for-ignition (TFI) range selection (For 5602/5603 units: On =10

seconds; Off =5 seconds. For 5605 units: On=10 seconds; Off =15 seconds).

Modulation and purge models of theVeri-Flame use all of the eight DIP switches, as illustrated in Figure 3.2 on page 13. They are as follows:

SW1: Recycling mode selection (On =Recycling; Off =Non-recycling)

SW2:Pilot selection (On=Intermittent,where pilot remains on during burner cycle; Off =Interrupted, where pilot valve closes after main burner is established).

SW3:Trial-for-ignition (TFI) range selection (For 5602/5603 units:On=10 seconds;

Off =5 seconds. For 5605 units: On=10 seconds; Off =15 seconds).

SW4 through 7: Purge time selection. Total purge time is the sum of each switch selected.

SW8: Post purge selection. (On=15 second post purge).

Eclipse Veri-Flame Instruction Manual 818 -2/02

12

Page 12
Image 12
Eclipse Combustion 5600 instruction manual DIP Switch Selection, Modulation & Purge DIP Switch Settings