LED STATUS

This section describes the status of operating conditions based on the LED or

 

combination of LEDs which are lit on the front cover of each Veri-Flame model.

 

Table 8.1 LED Status & Conditions forVeri-Flame No Purge Models

 

 

 

 

 

 

 

 

 

LED(S) LIT

 

POSSIBLE CAUSES

 

INTERLOCKS CLOSED

1) The interlocks are closed (normal operation), power on terminal 7.

 

 

 

 

 

 

 

 

 

SYSTEM ERROR

1) The flame detected is out of sequence, flame signal light is on.

 

 

2)

The sensor is “runaway”, flame signal light is on.

 

 

3)

Inductance is detected on sensor wires, flame signal light is on.

 

 

4)

Voltage wired into terminals 3, 4 or 5.

 

 

5)

Internal relay contacts welded.

 

 

6)

Internal controller failure.

 

 

7)

Main valve closed switch defective, no power to V.

 

 

 

 

 

 

 

 

 

FLAME FAILURE

1) Pilot flame is not established in selected TFI.

 

 

2)

Main flame is not established in selected TFI.

 

 

3)

Main flame fails within 35 seconds of TFI.

 

 

4)

Flame failed during operation in non-recycle mode.

 

 

5)

Flame failed 35 seconds after TFI and was not established after try in recycle mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Purge Model