TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | SOLUTION | |
Cannot initiate start sequence | Main valve is not closed. | Check main valve closed switch. | |
No voltage on V (or D). | |||
|
| ||
|
|
| |
|
| Check air pressure switch adjustment. | |
|
| Check air filter. | |
| Air pressure switch has not made | Check blower rotation. | |
| contact. | Check outlet pressure from blower. | |
|
| No voltage on 6 after 8 is on. | |
|
|
| |
|
| Check incomming gas pressure; adjust gas | |
|
| pressure if necessary. | |
| High gas pressure switch has tripped. | Check pressure switch setting and | |
|
| operation. | |
|
| No voltage to 7. | |
|
|
| |
|
| Check incomming gas pressure; adjust gas | |
|
| pressure if necessary. | |
| Low gas pressure switch has tripped. | Check pressure switch setting and | |
|
| operation. | |
|
| No voltage to 7. | |
|
|
| |
| Malfunction of flame safeguard system | Have qualified electrician investigate and | |
| such as a | ||
| rectify. | ||
| electrical noise in the sensor line. | ||
|
| ||
|
|
| |
| Purge cycle not completed. | Check switch settings. | |
| Check air switch. | ||
|
| ||
|
|
| |
| Main power is off. | Make sure power is on to control system. | |
|
|
| |
| No power to control unit. | Call qualified electrician to investigate. | |
|
|
| |
Scrambled messages on remote display. | Electrical interference. | Check grounding in system. | |
Separate communication cable. | |||
|
| ||
|
| Move ignition circuit. | |
|
|
| |
“UNSAFE AIR SHORT” message | Improperly adjusted air switch. | Check air switch settings. | |
Air switch either shorted or wired | |||
appears on display. | Check wiring to air switch. | ||
wrong. | |||
|
| ||
|
|
| |
Burner flame fails but no flame | A faulty scanner. | Check scanner as explained in checklists in | |
failure indication occurs. | “Maintenance” portion of this Section. | ||
| |||
|
| ||
|
|
| |
| Improperly connected sensor wires. | Check wiring diagram on page 20 or 21 as | |
| well as appropriate sensor information in | ||
|
| ||
|
| Section 6. | |
|
|
| |
| Electrical interference from other | Check Note information on page 24 | |
| current carrying wires. | regarding sensor wiring. | |
|
|
| |
Voltage reading greater than | Improper grounding. | Check grounding of neutral at control | |
15VDC at “Test Point” on | |||
power transformer. | |||
| |||
|
| ||
|
|
|