Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 Troubleshooting

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 29
Image 29

TROUBLESHOOTING

PROBLEM

POSSIBLE CAUSE

SOLUTION

Cannot initiate start sequence

Main valve is not closed.

Check main valve closed switch.

No voltage on V (or D).

 

 

 

 

 

 

 

Check air pressure switch adjustment.

 

 

Check air filter.

 

Air pressure switch has not made

Check blower rotation.

 

contact.

Check outlet pressure from blower.

 

 

No voltage on 6 after 8 is on.

 

 

 

 

 

Check incomming gas pressure; adjust gas

 

 

pressure if necessary.

 

High gas pressure switch has tripped.

Check pressure switch setting and

 

 

operation.

 

 

No voltage to 7.

 

 

 

 

 

Check incomming gas pressure; adjust gas

 

 

pressure if necessary.

 

Low gas pressure switch has tripped.

Check pressure switch setting and

 

 

operation.

 

 

No voltage to 7.

 

 

 

 

Malfunction of flame safeguard system

Have qualified electrician investigate and

 

such as a shorted-out flame sensor or

 

rectify.

 

electrical noise in the sensor line.

 

 

 

 

 

 

Purge cycle not completed.

Check switch settings.

 

Check air switch.

 

 

 

 

 

 

Main power is off.

Make sure power is on to control system.

 

 

 

 

No power to control unit.

Call qualified electrician to investigate.

 

 

 

Scrambled messages on remote display.

Electrical interference.

Check grounding in system.

Separate communication cable.

 

 

 

 

Move ignition circuit.

 

 

 

“UNSAFE AIR SHORT” message

Improperly adjusted air switch.

Check air switch settings.

Air switch either shorted or wired

appears on display.

Check wiring to air switch.

wrong.

 

 

 

 

 

Burner flame fails but no flame

A faulty scanner.

Check scanner as explained in checklists in

failure indication occurs.

“Maintenance” portion of this Section.

 

 

 

 

 

 

 

Improperly connected sensor wires.

Check wiring diagram on page 20 or 21 as

 

well as appropriate sensor information in

 

 

 

 

Section 6.

 

 

 

 

Electrical interference from other

Check Note information on page 24

 

current carrying wires.

regarding sensor wiring.

 

 

 

Voltage reading greater than

Improper grounding.

Check grounding of neutral at control

15VDC at “Test Point” on

power transformer.

Veri-Flame faceplate.

 

 

 

 

 

 

Eclipse Veri-Flame Instruction Manual 818 -2/02

29

Page 29
Image 29
Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 Troubleshooting, Problem Possible Cause Solution