Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 Specifications, Introduction

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 9
Image 9

Specifications

2

INTRODUCTION

Specifications

This section gives a detailed overview of Veri-Flame specifications and dimensions.

PARAMETER

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

Supply

• Series 5602 & 5605: 120 VAC (+10%, -15%), 50/60 Hz standard.

 

Series 5603: 240 VAC (+10%, -15%), 50/60 Hz standard.

 

 

Internal power consumption: 12 VA (excluding external connected loads).

Temperature Ranges

Unit

Model Nos.

 

 

Temperature Range

 

Veri-Flame

All Models

 

 

-40˚ to +60˚C

(-40˚ to +140˚F)

 

90˚ U.V. Scanner

5600-90A

 

 

-20˚ to +60˚C

(0˚ to 140˚F)

 

U.V. Scanner

5600-91

 

-20˚ to +125˚C

(0˚ to +257˚F)

 

NEMA4 UV Scanner

5600-91N4

 

-20˚ to +125˚C

(0˚ to +257˚F)

 

I.R. Scanner

5600-92B

 

-40˚ to +110˚C

(-40˚ to +230˚F)

 

UV/IR Scanner

5600-92SC

 

 

-20˚ to +80˚C

(0˚ to +176˚F)

 

Self-Check U.V.

5602-91

 

 

-20˚ to +60˚C

(0˚ to +140˚F)

 

Remote Display

5602DB

 

 

0˚ to 50˚C

(32˚ to 122˚F)

 

Remote Display

5602DBP

 

 

0˚ to 50˚C

(32˚ to 122˚F)

Flame Failure Response

3 seconds ±0.5 seconds.

 

 

 

 

Trial For Ignition (TFI)

No Purge & Purge Models:

 

 

 

 

 

Series 5602 & 5603: five or 10 seconds selectable.

 

 

Series 5605: ten or 15 seconds selectable.

 

 

Modulating Model: 5 or 10 seconds selectable

 

Pilot Interrupt (if selected)

10 seconds.

 

 

 

 

 

 

Purge Time

Selectable from 0-225 seconds in 15 second increments.

 

 

 

 

Terminals

 

 

UL, CSA

Relay Contact Rating

Output Ratings for 120 VAC

Function

 

 

 

Inductive Load

Resistive Load

Gas Valve

 

3, 5

 

175VA, 1/10 HP

10 amps

(maximum total connected

Ignition

 

4

 

 

375 VA

10 amps

load not to exceed 15 amps)

 

 

 

Motor or Contactor

 

8

 

470 VA, 1/2 HP

16 amps

 

 

 

 

Control Signal

 

A, 10, 11, 12, 13

 

 

175VA

10 amps

 

 

 

 

 

 

 

Relay Contact Rating

Output Ratings for 240 VAC

Function

Terminals

 

Resistive Load

Valves, Ignition

3, 4, 5,

 

 

 

5 amps

(maximum total connected

Motors or Contactor

8

 

 

 

 

16 amps

load not to exceed 15 amps)

 

 

 

 

Alarm

A

 

 

 

5 amps

 

 

 

 

 

Control

10, 11, 12, 13

 

5 amps

 

 

 

 

 

 

 

 

 

(continued onto next page)

Eclipse Veri-Flame Instruction Manual 818 -2/02

9

Page 9
Image 9
Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 instruction manual Specifications, Introduction