Table 9.1 Veri-Flame Operating Sequence (continued)
BURNER
Is voltage present at air flow switch
within ten seconds?
NO PURGE MODELS
MODULATION MODELS
PURGE MODELS
NORMAL MESSAGE
Is voltage present at air switch . . .
NORMAL MESSAGE
AIR PROVEN
Purge based on selected time.
Is voltage present at air switch . . .
| YES |
| NO |
|
|
|
|
ERROR MESSAGE
AIR PROVEN
NORMAL MESSAGE
PURGE TO HIGH FIRE
YES NO
ERROR MESSAGE
AIR NOT PROVEN XX:XX:XX LOCKOUT
AIR NOT PROVEN XX:XX:XX LOCKOUT
Modulator sent to high fire for selected purge time.
NORMAL MESSAGE
PURGE TO LOW FIRE
Modulator sent to low fire for selected purge time.
Is voltage present
at high purge switch?
| YES |
| NO |
|
|
|
|
NORMAL MESSAGE
PILOT TRIAL FOR
IGNITION
Spark and pilot valve energized for selected trial for ignition.
ERROR MESSAGE
HI DAMPER FAIL XX:XX:XX LOCKOUT
Is low fire switch closed?
YES NO
ERROR MESSAGE
LOW FIRE FAIL XX:XX:XX LOCKOUT
NORMAL MESSAGE
PILOT FLAME ON
Flame signal detected
NORMAL MESSAGE
PILOT FLAME XX.XV
TIME = XXXX:XX:XX
Spark turns off at end of TFI; sequence delayed 5 seconds.
NORMAL MESSAGE
MAIN FLAME ON
Is pilot flame signal present?
YES ![](/images/new-backgrounds/1053548/5354869xi4.webp)
NO
Is main flame signal present?
YES NO
Is flame signal present?
(see next page)
ERROR MESSAGE
PILOT FLAME FAIL XX:XX:XX LOCKOUT
ERROR MESSAGE
MAIN FLAME FAIL XX:XX:XX LOCKOUT