Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 Burner Shutdown

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 37
Image 37

Table 9.1 Veri-Flame Operating Sequence (continued)

BURNER SHUTDOWN

Shutdown is started by opening the operating interlock circuit.

Is voltage present at interlocks?

 

Continued operation.

 

 

 

 

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is post purge selected?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

 

 

 

 

 

 

 

 

 

 

 

NORMAL MESSAGE

POST PURGE

XX

Fuel valves de-energized; fan energized for 15 seconds.

Is main valve closed switch made?*

FOR PURGE & MODULATING

ERROR MESSAGE #1

UNSAFE AIR SHORT

If switch is opened within 30 seconds, sequence continues. If not, then . . .

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE AIR SHORT

XX:XX:XX LOCKOUT

Alarm energized.

YES NO

Is voltage present at air flow switch?

YES NO

ERROR MESSAGE #1

UNSAFE FLAME ON

Fan is energized. If signal is elimi- nated within 30 seconds, se- quence continues. If not, then . .

ERROR MESSAGE #2 – 30 SECONDS AFTER #1

UNSAFE FLAME ON

XX:XX:XX LOCKOUT

Alarm energized.

ERROR MESSAGE

MAIN VALVE FAIL XX:XX:XX LOCKOUT

Fan energized; alarm sounds.

Is flame signal present?

YES

NO

NORMAL MESSAGE

LIMITS OPEN

TIME = XXXX:XX:XX

* Applies to purge and no purge models only.

Eclipse Veri-Flame Instruction Manual 818 -2/02

37

Page 37
Image 37
Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 instruction manual Burner Shutdown