Eclipse Combustion 5600, VeriFlame Single Burner Monitoring System instruction manual Seconds

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 16
Image 16

System Errors & Lockout Conditions (Continued)

High to Low Fire Purge Modulation Capability with High to Low Fire Position Switch Interlocks

4)Low fire fail (for modulating model)–low fire switch open prior to trial for ignition.

5)High fire fail (for modulating model)–high fire switch is not closed at the end of high fire purge.

The following situations will result in a lockout condition:

6)Air failure (for purge and modulation models) – loss of combustion air anytime during the operational cycle. The Air Failure LED will be on for this condition. (See “Recycle Mode”).

7)Pilot flame fail (for all models) loss of flame during the trial for pilot ignition period. The Flame Failure LED will be on for this condition.

8)Main flame fail (for all models) loss of flame during the main burner trial for ignition or run period (recycling not selected). The Flame Failure LED will be on for this condition.

The following result in lockout conditions after 30 seconds, the system error light blinks about 14 times and then remains on:

9)If a flame is detected out of sequence, which may be caused by:

a)a faulty scanner (for all models);

b)electrical interference on the sensor wiring (for all models);

c)a flame exists in the burner or in the line of sight of a scanner, due to a gas leak, product fire or other condition (for all models).

10)Air flow switch closed before start-up (for purge and modulation models).

For modulation models: the modulation feature incorporates a high fire purge time and a low fire purge time into the purge sequence. This feature allows the Veri-Flame to sequence internal dry contacts which can be used by the customer requiring a high fire purge of the combustion chamber before ignition.

The high fire and low fire purge times are selectable by means of DIP switches (see Section 3,“DIP Switch Settings” on page 12):

SW4

15 seconds

SW6

................................ 60 seconds

SW5

30 seconds

SW7

............................. 120 seconds

The selected times are additive and apply to both the high fire and low fire purge times (that is, high and low fire times are always identical).

The modulation terminals will sequence as follows:

Sequence Step

Internal Contact Connections

 

 

 

Power Off

Terminal 10 (Common)

Terminal 11 (Auto)

Power On, Limits Open

Terminal 10 (Common)

Terminal 12 (Low Fire)

Purge To High Fire

Terminal 10 (Common)

Terminal 13

(High Fire)

 

 

 

 

Purge To Low Fire

Terminal 10 (Common)

Terminal 12

(Low Fire)

 

 

 

 

Automatic Modulation

Terminal 10 (Common)

Terminal 11

(Auto)

 

 

 

 

Alarm and Lockout

Terminal 10 (Common)

Terminal 12

(Low Fire)

 

 

 

 

The Automatic step occurs when the burners are operating and allows the burner firing rate to be controlled by an automatic temperature controller.

Eclipse Veri-Flame Instruction Manual 818 -2/02

16

Page 16
Image 16
Eclipse Combustion 5600, VeriFlame Single Burner Monitoring System instruction manual Seconds