![](/images/new-backgrounds/1053548/5354867x1.webp)
Table 9.1 Veri-Flame Operating Sequence
POWER ON
NORMAL MESSAGE
REMOTE DISPLAY REVISION X.X
Was internal safe start check successful?
| YES |
| NO |
|
| Various lockout messages |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
EXTERNAL INTERLOCK CHECKS
Is flame signal present?
ERROR MESSAGE #1
UNSAFE FLAME ON
Fan is energized. If signal is elimi- nated within 30 seconds, se- quence continues. If not, then . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON XX:XX:XX LOCKOUT
Alarm energized.
YES
FOR PURGE & MODULATING
ERROR MESSAGE #1
UNSAFE AIR SHORT
If switch is opened within 30 seconds, sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHORT
XX:XX:XX LOCKOUT
Alarm energized.
NORMAL MESSAGE
SAFE START OK
Check_Sum = XX
NORMAL MESSAGE
FAN ENERGIZED
Fan output is energized; modu- lator is sent to low fire.
| NO |
|
|
|
| Is main valve closed switch made?* |
| |||
|
|
|
|
|
|
|
| |||
|
| Is voltage present at air flow switch? |
|
|
| YES |
| NO |
| |
|
| YES | NO |
|
|
|
|
| ||
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ERROR MESSAGE |
| ||
|
|
|
|
|
|
|
|
MAINVALVE FAIL
XX:XX:XX LOCKOUT
Is voltage present at interlock switch?
| YES |
| NO |
|
|
|
|
ERROR MESSAGE
LIMITS OPEN
TIME = XXXX:XX:XX
Holds until answer is yes.
BURNER
(see next page)
* Applies to purge and no purge models only.
Eclipse