Eclipse Combustion 5600, VeriFlame Single Burner Monitoring System instruction manual AIR Failure

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 38
Image 38

 

 

Table 9.2

 

Remote Display Diagnostic Messages (Listed Alphabetically)

 

 

MESSAGE

TYPE

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

AIR FAILURE

Lockout

 

For purge & modulation models: Combustion air flow limit

 

 

XX:XX:XX LOCKOUT

 

 

switch opened for more than two seconds once initially proven.

 

 

 

 

 

 

 

 

AIR FAILURE

Status

 

For purge & modulation models: Combustion air flow limit switch

 

 

RECYCLING

 

 

opened; if “recycle” has been selected, the Veri-Flame will restart the

 

 

 

 

 

sequence after air failure (see “Recycle Mode” on page 14).

 

 

 

 

 

 

 

 

AIR NOT PROVEN

Lockout

 

For purge & modulation models: Combustion air flow limit

 

 

XX:XX:XX LOCKOUT

 

 

switch did not make within ten seconds of fan being energized.

 

 

 

 

 

 

 

 

AIR PROVEN

Status

 

For purge & modulation models: Combustion air flow limit

 

 

 

 

 

switch closed within ten seconds of fan being energized.

 

 

 

 

 

 

 

 

AUTOMATIC

Status

 

For modulation models only: Modulating motor is sent to au-

 

 

MODULATION

 

 

tomatic operation.

 

 

 

 

 

 

 

 

BURNER ON XX.XV

Status

 

Main flame of burner is proven in the automatic modulation mode;

 

 

TIME=XXXX:XX:XX

 

 

flame strength is XX.XV (volts DC). Elapsed time is shown in

 

 

 

 

 

hours:minutes:seconds.

 

 

 

 

 

 

 

 

D-INTERNAL FAIL

Lockout

 

For modulation models only: Internal control failure; replace

 

 

XX:XX:XX:XX LOCKOUT

 

 

controller.

 

 

 

 

 

 

 

 

FAN ENERGIZED

Status

 

For purge & modulation models: Blower motor is energized

 

 

 

 

 

at the start of pre-purge.

 

 

 

 

 

 

 

 

FLAME FAILURE

Lockout

 

Main flame lost during operation in the automatic modulation mode.

 

 

XX:XX:XX LOCKOUT

 

 

Burner number (X) given of failed unit.

 

 

 

 

 

 

 

 

HI DAMPER/POVC

Lockout

 

For modulation models only: High damper or high purge rate

 

 

XX:XX:XX LOCKOUT

 

 

switch did not make at the end of pre-purge to high fire.

 

 

 

 

 

 

 

 

K-INTERNAL FAIL

Lockout

 

Internal control failure; replace controller.

 

 

XX:XX:XX LOCKOUT

 

 

 

 

 

 

 

 

 

 

 

L-INTERNAL FAIL

Lockout

 

Internal control failure; replace controller.

 

 

XX:XX:XX LOCKOUT

 

 

 

 

 

 

 

 

 

 

 

LIMITS OPEN

Status

 

The controller has completed its internal checks and is standing by

 

 

TIME=XXXX:XX:XX

 

 

for the interlocks to close.

 

 

 

 

 

 

 

 

LOW FIRE FAIL

Lockout

 

For modulation models only: Low fire switch is open just prior

 

 

XX:XX:XX LOCKOUT

 

 

to pilot trial for ignition.

 

 

 

 

 

 

 

 

MAIN FLAME FAIL

Lockout

 

Main flame was not established during the main burner trial for

 

 

XX:XX:XX LOCKOUT

 

 

ignition.

 

 

 

 

 

 

 

 

MAIN FLAME FAIL

Status

 

Main flame lost during automatic modulation; control will recycle

 

 

RECYCLING

 

 

once if “recycle” has been selected.

 

 

 

 

 

 

 

Eclipse Veri-Flame Instruction Manual 818 -2/02