Eclipse Combustion 5600 instruction manual System Installation, Introduction

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 18
Image 18

System Installation

5

INTRODUCTION

Interlocks and Limit Switch Input

Combustion Air Switch Input

In this section, the necessary procedures are detailed to integrate aVeri-Flame into a burner system; Figures 5.1 and 5.2 illustrate the various terminal strips mentioned.

Note:

Shut off the power supply before theVeri-Flame is removed or replaced from the base.

Caution:

Installation and maintenance must conform with the National Electrical Code and all other national and local codes and authorities having jurisdiction. Flame monitoring systems must be installed by a qualified, licensed technician.

Wire external interlock, control, and limit switches in series to this input. Guard against induced voltage levels to wiring connected to this input. In some extreme wiring runs, reduction of induced voltages may require a load (relay or light) connected to terminal 7 to avoid system error lockouts. This input is the power source for the valve and ignition output terminals. Be sure all switches wired to this input can handle the current required by the total of all loads connected to terminals 3, 4,and 5.

For purge and modulation models: Wire any switches and contacts in series to this terminal for proving air flow function and relating to the air failure light. Power must not be immediately present at terminal 6 when power is first applied to terminals 1 or 7.

If this terminal is not used, place a jumper between the combustion blower out- put (terminal 8) and the air switch input (terminal 6).

If the combustion air blower is controlled outside of theVeri-Flame system, then a three way solenoid valve must be connected between the air switch port and the blower sensing port. The valve de-energized state should vent the switch to ambient pressure. The energized state then connects the air switch to the blower sensing port. Power the valve from the blower ouput terminal 8. If accepted by local codes, the air switch could be wired between the combustion blower output and the air switch input. Connecting the air switch in this man- ner will satisfy the open contact (air short) check on the switch.

Eclipse Veri-Flame Instruction Manual 818 -2/02

18

Page 18
Image 18