Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 instruction manual AIR Failure

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 31
Image 31

Table 8.2 LED Status & Conditions forVeri-Flame Purge Models

LED(S) LIT

 

POSSIBLE CAUSES

INTERLOCKS CLOSED

1) The interlocks are closed (normal operation), power on terminal 7.

 

 

 

 

SYSTEM ERROR

1) The flame detected is out of sequence, flame signal light is on.

 

2)

The sensor is “runaway”, flame signal light is on.

 

3)

Inductance is detected on sensor wires, flame signal light is on.

 

4)

Voltage wired into terminals 3, 4 or 5.

 

5)

Internal relay contacts welded.

 

6)

Internal controller failure.

 

7)

Air flow switch closed before start-up.

 

8)

Main fuel valve switch opens after shutdown or before start-up, no power to V.

 

 

 

 

FLAME FAILURE

1) Pilot flame is not established in selected TFI.

 

2)

Main flame is not established in selected TFI.

 

3)

Main flame fails within 35 seconds of TFI.

 

4)

Flame failed during operation in non-recycle mode.

 

5)

Flame failed 35 seconds after TFI and was not established after one try in recycle mode.

 

 

 

 

AIR FAILURE

1) Air flow switch not closed within ten seconds of start-up.

 

2)

Air flow switch is open during timing cycle.

 

3)

Air flow switch is open during firing cycle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Purge Model

Eclipse Veri-Flame Instruction Manual 818 -2/02

31

Page 31
Image 31
Eclipse Combustion VeriFlame Single Burner Monitoring System, 5600 LED Status & Conditions forVeri-Flame Purge Models