Eclipse Combustion 5600, VeriFlame Single Burner Monitoring System instruction manual Yes

Models: 5600 VeriFlame Single Burner Monitoring System

1 42
Download 42 pages 8.53 Kb
Page 36
Image 36

Table 9.1 Veri-Flame Operating Sequence (continued)

BURNER START-UP (continued)

NORMAL MESSAGE

MAIN FLAME ON PILOT OFF

Is flame signal present?

YES NO

NORMAL MESSAGE

MAIN FLAME ON

 

 

 

 

 

IF Interrupted Pilot is selected

 

IF Intermittent Pilot Is Selected

 

 

 

 

 

ERROR MESSAGE

MAIN FLAME FAIL XX:XX:XX LOCKOUT

NORMAL MESSAGE

MAIN FLAME ON

Pilot will shut off 10 seconds after main flame is energized.

MODULATION MODELS

PURGE & NO PURGE MODELS

NORMAL MESSAGE

 

AUTOMATIC

MODULATION MODELS

MODULATION

Modulator sent to automatic 20 seconds after main valve is energized.

NORMAL MESSAGE

 

BURNER ON XX.XV

 

TIME = XXXX:XX:XX

PURGE & NO PURGE MODELS

Main flame of burner is proven. Flame signal = XX.XVolts DC; elapsed time is shown in hours: minutes:seconds.

Is flame signal present?

YES

NO

Is air switch signal on?

Is recycle selected?

YES NO

Is recycle selected?

YES NO

Was the main flame on more than 35 seconds?

YES NO

Was the main flame on more than 35 seconds?

YES NO

ERROR MESSAGE

MAIN FLAME FAIL

ERROR MESSAGE

MAIN FLAME FAIL

YES NO

ERROR MESSAGE

AIR FAILURE

RECYCLING

Unit returns to beginning sequence.

ERROR MESSAGE

AIR FAILURE XX:XX:XX LOCKOUT

RECYCLING

Unit returns to beginning sequence.

XX:XX:XX LOCKOUT

Eclipse Veri-Flame Instruction Manual 818 -2/02

36

Page 36
Image 36
Eclipse Combustion 5600, VeriFlame Single Burner Monitoring System instruction manual Yes