Table 9.2 Remote Display Diagnostic Messages (continued)

 

 

MESSAGE

TYPE

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

UNSAFE FLAME ON

Hold

 

Flame signal—actual, induced, or runaway scanner—is detected be-

 

 

 

 

 

 

fore start-up or after shutdown. The fan is energized. If the cause is

 

 

 

 

 

 

corrected within 30 seconds, as in afterburn, the control will turn

 

 

 

 

 

 

off the fan and continue the sequence.

 

 

 

 

 

 

 

 

 

UNSAFE FLAME ON

Lockout

 

Same conditions as above, except the cause has not been corrected

 

 

XX:XX:XX LOCKOUT

 

 

 

within 30 seconds, resulting in a lockout and the alarm being energized.

 

 

 

 

 

 

 

 

 

UNSAFE–FLM–PURGE

Hold

 

For purge & modulation models: Flame signal—actual, induced,

 

 

 

 

 

 

or runaway scanner—is detected during the selected purge time

 

 

 

 

 

 

period. The fan is energized. If the cause is corrected within 30 sec-

 

 

 

 

 

 

onds, as in afterburn, the control will turn off the fan and continue

 

 

 

 

 

 

the sequence.

 

 

 

 

 

 

 

 

 

UNSAFE–FLM–PURGE

Lockout

 

For purge & modulation models: Same conditions as above,

 

 

XX:XX:XX LOCKOUT

 

 

 

except the cause has not been corrected within 30 seconds, resulting

 

 

 

 

 

 

in a lockout and the alarm being energized.

 

 

 

 

 

 

 

 

 

V–INTERNAL FAULT

Lockout

 

Internal control failure; replace controller.

 

 

XX:XX:XX LOCKOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

WATCHDOG FAIL

Lockout

 

Internal control failure; replace controller.

 

 

XX:XX:XX LOCKOUT

 

 

 

 

 

 

 

 

 

 

 

 

 

XXXXXXX

Status

 

In combination with other messages, shows the control is in the

 

 

XXXXXTESTXX

 

 

 

minimum pilot test mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 