UM581127000 | User Instructions |
Issue AB, March 22, 2012 | Spec. No. 581127000 (Model 710NPBA) |
|
|
Optional Manual Battery Disconnect Circuit Card
The optional manual battery disconnect circuit card contains a manual battery disconnect switch and indicator. Refer to Figure
J2 |
J1 |
S1 |
Manual Battery Disconnect Switch
Manual Battery Disconnect | Illuminates if the Battery Disconnect Contactor has |
Active Indicator | been manually disconnected (placed in open position). |
Momentary UP / Middle / Momentary Down
Momentary UP Position: | Closes (latches in close position) the Battery Disconnect Contactor. |
Middle Position: | Normal Operation. |
Momentary DOWN Position: Opens (latches in open position) the Battery Disconnect Contactor. Momentarily place switch in the UP position to close the contactor.
Figure
Optional Manual Battery Disconnect Circuit Card (P/N 540973)
Page 8 | Chapter 2. Operating Procedures |
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy