UM581127000 User Instructions
Issue AB, March 22, 2012 Spec. No. 581127000 (Model 710NPBA)
Page 46 Chapter 4. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-16 Replacing a Distribution Panel
Componentsremoved in illustration for clarity only.
Front Front
Battery
Distribution
Panel
Load
Distribution
Panel
GroundBusbar
Hardware
GroundBusbar
Hardware
BatteryBusbar
Hardware
DistributionPanel
Hardware
SystemLoad
DistributionBusbar
Hardware
DistributionPanel
Hardware
ShortingBlock if 4th shelf
hasConverter Option.
Ifmore than three shelves with the
ConverterOption, /48/ jumpers.
Assemblyorder is: lug,1/4" flat washer, 1/4" lock washer,
1/4-20nut. Torque to 84 in-lbs. Note that a shorting block
willbe factory installed in thisdistributiondevice position.
/48/jumpers.
Assemblyorder is: lug,1/4" flat washer,
1/4"lock washer, 1/4-20 bolt.
Torqueto 84 in-lbs.
ListDA Dual Voltage
DistributionPanel
(ListsDB, DC, and DD similar.)