to ensure that it cannot be pulled out of the terminal block. Repeat for each wire
to be reconnected.
13) Remove the grounding wrist strap.
14) Close the distribution cabinet’s front door. Turn the latch clockwise to secure the
door.
15) Enable the external alarms, or notify appropriate personnel that this procedure is
finished.
16) Ensure that there are no local or remote alarms active on the system.
Figure 4-10
IB2 (ACU+ Interface Board) Connector Locations
J3-J9:
Wire Size Capacity: 16-26AWG.
RecommendedTorque: 2.2 in-lbs.

-

J12
*