to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be reconnected.

13)Remove the grounding wrist strap.

14)Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.

15)Enable the external alarms, or notify appropriate personnel that this procedure is finished.

16)Ensure that there are no local or remote alarms active on the system.

TEMPEX

PROBE2

TEMPEX PROBRE1

Connector ACU+to

IB2 Board Assembly

 

 

 

J12

J11

J2

 

 

 

 

 

+

 

 

Blocks

-

 

2 1

 

 

J3

31

 

3

 

 

 

 

 

 

4 2

 

 

Terminal

J4

13 5

 

6

 

 

 

6

 

 

 

 

 

 

2 4

 

 

 

 

 

 

4 5

 

 

Input

 

1 5

 

6

 

 

 

 

8

 

 

 

 

 

 

7

 

 

 

 

 

 

2

 

 

Digital

 

 

 

4

 

J10

J5

5 3

 

6

 

 

 

NC

 

NC

2

 

Relay Output Terminal Blocks

J9 J8 J7 J6 NO 7C NC NO 5C NC NO 3C NC NO 1C *

5 3 1 5 3 1 5 3 1 5 3 1

NO C NC NO C NC NO C NC NO C

6 4 2 6 4 2 6 4 2 6 4 8 6 4 2

RELAY

J3-J9:

Wire Size Capacity: 16-26 AWG.

Recommended Torque: 2.2 in-lbs.

Figure 4-10

IB2 (ACU+ Interface Board) Connector Locations