UM581127000

User Instructions

Issue AB, March 22, 2012

Spec. No. 581127000 (Model 710NPBA)

 

 

 

 

 

 

 

 

 

Replacing a TPL-B Fuse

 

 

 

 

 

 

 

Procedure

 

 

Note: Refer to Figure 4-4as this procedure is performed.

1)Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.

2)Remove the fuse case from the mounted fuse block by grasping its handle and pulling it straight out.

3)Open the fuse case.

4)Remove the open fuse from the fuse case and replace it with the same type and rating.

5)Close the fuse case.

6)Push the fuse case securely back into the mounted fuse block.

7)Replace the alarm fuse located in the front of the TPL-B fuse block. Replace only with a fuse of the same type and rating. Ensure that a plastic safety cover is installed on the alarm fuse.

8)Close the distribution cabinet’s front door. Turn the latch clockwise to secure the door.

GMT-18/100A Alarm Fuse (P/N 248610301) and GMT-X Safety Fuse Cover (P/N 248898700)

(Both are provided w/ fuseblock)

Fuse Installed in

Open Fuse Case

(rear view)

TPL Fuse

Fuse Case

Fuse Installed in

Closed Fuse Case

(rear view)

Open Fuse Case View

Fuseblock (P/N 516241)

Figure 4-5

Replacing a TPL-B Fuse