UM581127000 User Instructions
Issue AB, March 22, 2012 Spec. No. 581127000 (Model 710NPBA)
Page 50 Chapter 4. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-19
Replacing a Load Disconnect Contactor
in a 1-Row Distribution Cabinet
Load
Disconnect
Contactor
Componentsremoved in
illustrationfor clarity only.
Front
5/16-18x 1Bolt
5/16"Belleville Lock Washer
5/16"Belleville Lock Washer
(concaveside of Belleville
LockWashers face each other)
5/16"Hardened Flat Washer
(4places)
Torqueto 100 in-lbs.
Applyelectrical anti-oxidizing
compoundto busbar
matingsurfaces.
Contactorstyles vary
betweenmanufacturers.
BlackWire
Violet/WhiteWire
VioletWire
RedWire
Violet/WhiteWire
VioletWire BlackWire
RedWire