User Instructions UM581127000
Spec. No. 581127000 (Model 710NPBA) Issue AB, March 22, 2012
Chapter 3. Maintenance Page 9
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CHAPTER 3. MAINTENANCE

SYSTEM MAINTENANCE PROCEDURES

It is recommended to perform the maintenance procedures listed in Table 3-1 every
6-months to ensure continual system operation.
PROCEDURE
REFERENCED IN
COMPLETED (√)
Check ventilation openings for
obstructions such as dust,
papers, manuals, etc.
--
Inspect and tighten all
installer's connections.
IM581127000,
Chapter 4.
Making Electrical
Connections.
Note: This table may be reproduced as necessary to record and document
system performance.
Table 3-1
Maintenance Procedures to be Performed at 6-Month Intervals

ADDING A RECTIFIER OR DC-DC CONVERTER MODULE

TO AN EXISTING MODULE MOUNTING ASSEMBLY

To increase system current capacity, a rectifier module can easily be added to an existing
module mounting assembly that contains an empty rectifier module mounting position.
Likewise, in systems that accept DC-DC converter modules, to increase subsystem
capacity a DC-DC converter module can be added to a module mounting assembly that
contains an empty converter module mounting position.
The module location diagram on the front of each module mounting assembly shows
which type of module can be operated in that shelf. (See Figure 3-1.) Rectifier modules
will operate in any mounting position in any shelf. If a shelf accepts DC-DC converter
modules, they must be installed in any or all of the four middle mounting positions (B, C,
F, G) of each 8-position module mounting shelf.
It is recommended that the current limit point be checked whenever a rectifier is added to
or removed from the power system. Refer to “Checking the ACU+ Current Limit Point
after Adding or Removing a Rectifier” in “CHAPTER 4. TROUBLESHOOTING AND
REPAIR”.
The rectifier or converter module being added is assigned by the ACU+ the lowest
available identification number. If desired, you can change the identification number, see
“Configuring the ACU+ Identification of Rectifier Modules” or “Configuring the ACU+
Identification of Converter Modules” in Chapter 5 of the separate Power System
Installation Manual (IM581127000).